User`s guide

The grey
side of the
ECL Card
Extended service
Service parameter(s) 44-51
32m
44 Max. DHW charging time
Circuit Setting range Factory setting
I 0 ... 250 min. 0 min.
When the set max. DHW charging time expires, the charging is
deactivated.
0: If the DHW temperature is lower than the
DHW charging cut-in temperature (line 195),
the charging remains active for unlimited
time. If the DHW temperature is higher than
the DHW charging cut-in temperature, the
charging is deactivated after 35 min.
1 ... 250:
The charging is deactivated when the set
time expires.
45 DHW charging deactivation time
Circuit Setting range Factory setting
I 0 ... 250 min. 0 min.
If the charging time has reached its maximum (line 44), the
charging is deactivated for the set time.
0: No deactivation time.
1 ... 250 :
When the DHW charging time has reached
its maximum, DHW can only be charged
again when the deactivation time has
expired.
51 DHW charging pump / changeover valve
Circuit Setting range Factory setting
I ON / OFF OFF
Determine whether you have a DHW charging pump or a
changeover valve.
ON: Changeover valve P2. The circulation pump
P1 is running during DHW charging
OFF: DHW charging pump P2. The heating
circulation pump P1 is stopped during DHW
charging*.
* See line 43 for parallel operation