32b
Service parameter(s) 13
13 Reference ramping
Circuit Setting range Factory setting
(I) / (II) 0 ... 99 min. (0) / (0) min.
The time in which the desired flow temperature increases slowly
to avoid load peaks in the heat supply.
Set the ramping time for the controller.
Temperature °C
Setting line 13 Time (min.)
In order to avoid load peaks in the supply network, the flow
temperature can be set to increase slowly after a period with
setback temperature. This causes the valve to open slowly.