User`s guide
Control & overviews
Service parameters (10-199)
31a
Circuit I (Heating and DHW)
Lines Setting ranges Factory settings Your settings
10 Choice of room panel / remote control
0 ... 5 5
11 Setback temperature dependent
on outdoor temperature
OFF / -29 ... 10 °C -15 °C °C
13 Reference ramping
0 ... 99 min. 0 min. min.
14 Optimizing time constant
OFF / 10 ... 59 OFF
15 Adaptive function of room
temperature
OFF / 1 ... 30 OFF
17 Influence on desired flow temperature
OFF / 1 ... 20 K OFF K
20 Optimization based on room /
outdoor temperature
ON / OFF OFF
21 Total stop
ON / OFF OFF
22 Pump exercise
ON / OFF ON
23 Valve exercise
ON / OFF OFF
24 Gear motor / thermo actuator
ON / OFF ON
30 Return temperature limitation
10 ... 110 °C 60 °C °C
31 Return temperature limitation
- upper limit (X-axis)
-60 ... 20 °C 15 °C °C
32 Return temperature limitation
- upper limit (Y-axis)
10 ... 110 °C 40 °C °C
33 Return temperature limitation
- lower limit (X-axis)
-60 ... 20 °C -15 °C °C
34 Return temperature limitation
- lower limit (Y-axis)
10 ... 110 °C 60 °C °C
35 Return temperature influence
- max. limitation
-9.9 ... 0 ... 9.9 -2.0
36 Return temperature influence
- min. limitation
-9.9 ... 0 ... 9.9 0.0
37 Time constant for return temperature
limitation
OFF / 1 ... 50 25
40 DHW pump post-run (P2)
0 ... 9 min. 0 min. min.
41 DHW charging pump post-run (P5)
0 ... 9 min. 0 min. min.