Installation guide
InstallationGuideECLComfort210/310,applicationA214/A314
5.6Compensation1
Limit(compensationtemp.,1.point)
11060
CircuitSettingrange
Factorysetting
1
–20...80°C5°C
Setthecompensationtemperaturelimitpoint1.
Inuence
°C
+
-
Temp.S1
Compensation1
In.-max.(compensationtemp.,1.point)
11062
CircuitSettingrange
Factorysetting
1
-9.9...9.90.0
Determineshowmuchthedesiredowtemperaturewillbeinuencedifthe
compensationtemperatureishigherthanthesetlimit.
Inuencehigherthan0:
Inuencelowerthan0:
Example
In.-min.(compensationtemp.,1.point)
11063
CircuitSettingrange
Factorysetting
1
-9.9...9.90.0
Determineshowmuchthedesiredowtemperaturewillbeinuencedifthe
compensationtemperatureislowerthanthesetlimit.
Inuencehigherthan0:
Inuencelowerthan0:
Example