Installation guide
InstallationGuideECLComfort210/310,applicationA214/A314
5.5LimitTsafety
LimitTfrost(slidingfrostprotection)
11108
CircuitSettingrange
Factorysetting
1
OFF/0...50°C10°C
OFF:
0...50:
In.-min.(min.inuence)
11105
CircuitSettingrange
Factorysetting
1
0.0...9.92.0
Determineshowmuchthedesiredow/ducttemperaturewillbeincreased
iftheS5temperatureislowerthanthesetvaluefor'LimitTfrost'.
0.0:
0.1...9.9:
Example
Adapt.time(adaptationtime)
11107
CircuitSettingrange
Factorysetting
1
OFF/1...50sOFF
ControlshowfasttheS5temperatureadaptstothedesired'LimitTfrost'(I
control).
OFF:
1:
50: