Installation guide
InstallationGuideECLComfort210/310,applicationA214/A314
A214.4
Heatingandcoolingwithducttemperaturecontrol:
TypicalA214.4application:
S 4
P 2
F1
S 1
Da nfos s
87 H21 22.10
ECL 210 / (310)
R4 (R6)
S 5
M1
S 6
X3
S 7
M2
S 3
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Compensationtemperaturesensor(notillustrated)
S3
Flowtemperaturesensor,heatingcircuit
S4Ducttemperaturesensor
S5Returntemperaturesensor
S6
Frosttemperaturesensor
S7
Frostthermostat
S8
Firealarminput(notillustrated)
M1
Motorizedcontrolvalve,heating
M2
Motorizedcontrolvalve,cooling
F1Fan
P2Damper
X3
Circulationpump
R4
Relayoutput,alarm,ECLComfort210
(R6)
Relayoutput,alarm,ECLComfort310