Installation guide
InstallationGuideECLComfort210/310,applicationA214/A314
Alarmtime-out
11637
CircuitSettingrange
Factorysetting
1
0...240s0s
Therealarm,basedontherethermostat,isactivatedwhenthere
thermostathasbeenactivatedforalongertime(inseconds)thantheset
value.
0...240:
5.12.5Temp.monitor.
Upperdifference
11147
CircuitSettingrange
Factorysetting
1
OFF/1...30KOFF
Thealarmisactivatediftheactualow/ducttemperatureincreasesmore
thanthesetdifference(acceptabletemperaturedifferenceabovethedesired
ow/ducttemperature).Seealso'Delay'.
OFF:
1...30K:
Flow/ducttemp.°C
Upperdifference(set
value)
Desiredow/duct
temp.
Time
Lowerdifference
11148
CircuitSettingrange
Factorysetting
1
OFF/1...30KOFF
Thealarmisactivatediftheactualow/ducttemperaturedecreasesmore
thanthesetdifference(acceptabletemperaturedifferencebelowthedesired
ow/ducttemperature).Seealso'Delay'.
OFF:
1...30K:
Flow/ducttemp.°C
Lowerdifference(set
value)
Desiredow/duct
temp.
Time
Delay
11149
CircuitSettingrange
Factorysetting
1
1...99m10m
Ifanalarmconditionfromeither'Upperdifference'or'Lowerdifference'is
presentforalongertimethanthesetdelay(inmin.),thealarmfunction
isactivated.
1...99m:
Temp.
Flowtemp.
Alarmlimit
Time
Delay