Installation guide
InstallationGuideECLComfort210/310,applicationA214/A314
5.12.2LimitTfrost
Alarmvalue
11656
CircuitSettingrange
Factorysetting
1
–20...20°C6°C
Whentheactualtemperature,measuredbyS5,getsbelowthesetvalue,the
frostalarmwillbeactivated.
–20...20:
5.12.3Frostthermostat
Alarmvalue
11616
CircuitSettingrange
Factorysetting
1
0/1
0
AfrostthermostatcanbeconnectedtotheS7input.Whenthetemperature,
measuredbythefrostthermostat,getsbelowthesetvalue,theS7input
willbeactivated.
Thefrostalarmcanbeactivatedwhenthecontactsinthefrostthermostat
openorclose.
0:
1:
Alarmtime-out
11617
CircuitSettingrange
Factorysetting
1
0...240s0s
Thefrostalarm,basedonthefrostthermostat,isactivatedwhenthefrost
thermostathasbeenactivatedforalongertime(inseconds)thantheset
value.
0...240:
5.12.4Firesafety
Alarmvalue—A214
11636
CircuitSettingrange
Factorysetting
1
0/1
0
ArethermostatcanbeconnectedtotheS8input.Whenthetemperature,
measuredbytherethermostat,getsabovethesetvalue,theS8inputwill
beactivated.
Therealarmcanbeactivatedwhenthecontactsintherethermostat
openorclose.
0:
1: