10304
CircuitSettingrange
Factorysetting
1
1...1008
ThelteringofthemeasuredtemperatureatS4preventsinstabilityinthe
controloftheducttemperature.
Thesetvalueisanindirecttimeconstant.Theresultingtimeconstantis
listedintheexamplesbelow.
Lowvalue:

Highvalue:













Accum.lterA214.4/A214.5/A314.1/A314.2
11082
CircuitSettingrange
Factorysetting
1
1...250s25s
Thevaluedeterminesthelteringofthedesiredow/ducttemperaturein
ordertochangecorrectlyfromheatingtocoolingmodeorviceversa.
Thesetvalueisanindirecttimeconstant.Theresultingtimeconstantis
listedintheexamplesbelow.
Lowvalue:
Highvalue:




















Duct/roomtemp.
Deadzone(IDno.
11009)
Heating
°C
Cooling
Actual