Appendix 3 - continued
Situation 5
Change of setting in a controller from a PC
Objective
To make a setting in a plant via the AKM programme.
E.g.:
• Change of a temperature
• Change of a manual defrost
• Start/stop of refrigeration in an appliance
Condition
The system must be operating.
Procedure
1. Activate the AKA" - "Controllers.. function.
2. Select the relevant network and the required controller.
3. Find the document “Menu operation via AKM”. It must be
the document that deals with the relevant controllers order
number and software version.
4. Proceed by pushing “OK”. The controller’s list of functions will
now be shown.
5. Now find the function that has to be changed (refer to the men-
tioned document, so that it will be the right one).