26 Installation guide RI8BP602 © Danfoss 10/2011 AKM/AK Monitor/AK Mimic
Appendix 3 - continued
4. If log setups have to be defined, it may be done in the following
way:
The collection of logs must take place in the plant’s master
gateway and there must be automatic transfer of data from the
master gateway to the central PC.
a) Establish the required logs and select the type called AKA
log”. Read the AKM Manual.
When the log has been defined, remember to:
- Start the log
- Push the Automatic collect function
b) You must now define how the collection of logs is to be
presented. Read the AKM Manual. If automatic printout of
the collected data is required on the central PC, remember
to activate the Auto print” function.
5. The receiver of the alarm must be the master gateway at the
central PC to which a printer has been connected. The alarms
will subsequently be rerouted to the central PC.
a) Select AKA
b) Select the plants master gateway (1:125)
c) Push Alarm and the gateway’s alarm receiver display will
appear
d) Select “Enable” (the controllers will now be able to retransmit
the alarms to the master gateway)
e) Select retransmission of the alarms by a push on “System
address”
f) Enter system address on the alarm receiver (241:125)
g) Select master gateway of the central plant (241:125)
h) Push Alarm and the gateway’s alarm receiver display will
appear
i) Select retransmission of the alarms by a push on AKA Alarm
schedule”
j) Push "Setup"
k) On the first line “Default destinations” the following values
are set:
Primary at 240:124
Alternative at 241:125
Copy at 241:125
Select DO2
l) Push "OK"
m) In the subsequent display, set the following in the first field
“Default destinations”:
Primary = Alarm
Alternative = AKA Printer
Copy = AKA Printer
5d - 5f
5g - 5j
241:125