Installation guide

AKM/AK Monitor/AK Mimic Installation guide RI8BP602 © Danfoss 10/2011 25
Appendix 3 - continued
Situation 3
First communication to a plant from a central PC
Objective
Via the central PC
- to know the plant structure
- to give the plant some customer-adapted names
- to define a plant overview
- to define logs
- to define the alarm system
Conditions
• New installation
The plant has been prepared, as explained in “Example 1”
The central PC has been prepared, as explained in “Example 2”.
(Also the last point concerning new router lines).
Procedure
1. The AKM programme is now ready to obtain data on the plant
configuration.
If the AKM programme has just been installed, it will not
recognise files of the “Default description file” type. The
programme must know these files, and it can be arranged in
two stages:
a) Import:
If you have copies of such files on a disc, you can copy them
into the programme by means of the “Import Description
file” function. Read the AKM Manual. If you do not have
such copies, just proceed from here. It will just take a little
longer to obtain the data.
b) Upload:
This function will obtain the plant configuration as well as
the “Default Description files” which the programme has not
obtained via the import function mentioned under point
a. Use the “Upload” function and select the two fields “Net
configuration and AKC description”. Read the AKM Manual.
2. Now assign a name to all the controllers with the “ID-code” func-
tion. Read the AKM Manual.
3. If plant overviews have to be defined, i.e. screen displays where
only selected measurements or current settings are shown, do
it, as follows.
The definition must be made in several stages:
a) First define the measurements and settings to be shown.
This is done by editing customer-adapted description files,
as described in the AKM Manual. If you however have corre-
sponding files from an earlier system, you can import them
with the function mentioned under point 1a.
b) Now connect the relevant customer-adapted description
files. Read the AKM Manual.
c) The different screen displays can now be defined. Read the
AKM Manual.
240:124
241:120
241:125
1:125