Installation guide
AKM/AK Monitor/AK Mimic Installation guide RI8BP602 © Danfoss 10/2011 17
2. Connection
3. Set port on AKA 245
4. Set router lines
Gateway
The supply voltage to the converter to be connected, as illustrated
(via DO1 on AKA 245).
AKA 245 can then reset the server. The converter will also be
switched on and the start-up controlled when AKA 245 is switched
on.
Data communication between AKA 245 and the converter to be
made with the specified cable.
PC
Connection to a PC to be made as described in section 1 above.
RS232 port
Baud rate
Keep the setting at 9600 until the whole communication functions
correctly. It may subsequently be raised to 38400.
Addresses
Set the addresses that have been set in the connected TCP/IP con-
verter (IP address, IP-GW address and Subnet Mask).
Keep the remaining settings unchanged, but check one character
in ”Initiate string”. At Digi One it should read ”..Q3…”.
DANBUSS port
See AKM Manual.
AKA 245
Select the AKA setup in AKM.
Router lines must be set as indicated in the AKM Manual. When
there is a network at another converter, the converters IP address
must be set. (Like for modem. Just set an IP address instead of a
telephone number).
AKM
Select the AKM setup in AKM.
Router lines to be set as mentioned earlier.
Remember to select TCP/IP in "Channel" and type in "Initiate", if a
converter is connected to the Com port.
ALTERNATIVELY, select WinSock in "Channel" and nothing in "Initi-
ate", if connection takes place via the net card.
Appendix 1 - continued
Digi One SP