Installation guide

AKM/AK Monitor/AK Mimic Installation guide RI8BP602 © Danfoss 10/2011 11
3. Set the numbers for "Domain", "Subnet" and "Network" in the
field:
4. Enter the IP address of the unit to which you wish to establish a
connection
5. Select the port (channel) "SC.Winsock"
6. Select the "SC" field
7. Enter the Authorization code which is set in AK-SC 255 /355/CS
8. Enter the Account Number which is set in AK-SC 255/355/CS
9. Enter the Alarm port number which is set in AK-SC 255/355/CS
10. Finally, press "Insert"
(If modifying data of an existing plant, press "Update")
The connection is ready once these settings have been made.
The next step is to 'see' which controllers are found at the plant. This
setting should be done later.
2. Press the "Service" key
Information
This is where the new AK-SC, AK-CS
or AK-SM plants must be set up.
This is also where users can modify
existing plants.
Information
To the left:
D = Domain
S = Subnet
N = Network
On the right-hand side of the field you can enter the name, so that the
plant is easier to recognise in day-to-day operations.
Information
Here, it is only the "SC. Winsock" port that is used in the connection to
AK-SC 255.
In other situations, a modem connection and a corresponding initiali-
sation string can be selected.
(the IP address 87.54.48.50:80, for example)
The number after the colon is the number of the communication port.
In this example 80 is selected.
Information
Port 3001 is a default value.
Factory setting
Authorisation code = 12345
Account no. = 50
(User name and password are always numeric)