Product Overview
19
www.HEATING.DANFOSS.us | www.RadiatorControl.com | E-mail: heating.cs.na@danfoss.com | Fax: 416-352-5981 | Tech Support: 1-888-DANFOSS (326-3677)
Please see datasheets for complete technical specications available online at heating.danfoss.us.
4-Way Mixing
4-WAY MIXING
ESBE VRG Code No.
Description
Connection
Cv Body Series
Size Type
193B1531 3/4”
FNPT
4.7
4 Way DZR Brass VRG 141
193B1532 3/4” 7.3
193B1533 1” 11.7
193B1534 1-1/4” 18.7
193B1535 1-1/2” 29.3
193B1536 2” 46.8
193B1537 3/4"
Solder
2.9
193B1538 1" 7.3
193B1539 1 1/4" 13.9
ESBE Series VRG140 4 Way Mixing Valve is a range of compact, low leakage mixing valves. For easy manual operation
the valves are equipped with non-slip knobs and end stops for an operational angle of 90°. The valve position scale can be turned over and
rotated allowing many dierent mounting positions. Together with ARA600 and Series 90 actuators, the VRG valves are easily automated and
have excellent regulating accuracy due to the unique valve to actuator interface.
DIN Flange & Gaskets Sets for use with ESBE “F” Series 4-way mixing valves.
DIN
Flanges / Gaskets
Code No. Size Description
065F8950 2"
DIN Flange
(Four Flanges Required per 4 Way Valve)
082F8961 2-1/2”
082F8962 3”
082F8963 4”
082F8964 5”
082F8965 6”
065F8951 2"
Gasket for DIN Flange
(Four Gaskets Required per 4 Way Valve)
082F8966 2-1/2”
082F8967 3”
082F8968 4”
082F8969 5”
082F8970 6”
ESBE
Type F
Code No.
Description
Connection
Cv Body Reference
Size Type
065B6150 2"
DIN
Flange
75
4 Way Cast Iron
4 F 50
065B6165 2-1/2” 105 4 F 65
065B6180 3” 175 4 F 80
065B6200 4” 265 4 F 100
065B6225 5” 325 4 F 125
065B6250 6” 465 4 F 150
ESBE Type F 4-way valves are designed for use in commercial or residential heating and cooling systems, to control and
distribute water or non-corrosive liquids to dierent zones. The ESBE four-way valve features a double mixing function. When hot water
from the boiler is mixed with the return water, the temperature of the returned water rises (higher than can be achieved with a 3- way valve),
reducing the risk of condensation and assuring a longer boiler life. The mixing proportions can be adjusted manually, or in automatically
controlled applications, by means of a control actuator. The scale is graduated on both sides and can be turned, allowing a choice of mounting
positions.