Provide power supply and electrical protection
Requirements:
An additional external overload protection is
still advisable for either alarm or manual reset.
For overload setting, take the max current
you can face on the application and add
10%. Setting must always be lower than Max
Operating Current (see table Three phase
electrical characteristics” from the section
“Electrical data, connections and wiring”)
HP safety switch and DGT must be wired in the
safety chain. Other safety devices such as LP can
be either hardware or software managed.
Provide separate electrical supply for the
heaters so that they remain energized even
when the machine is out of service (e.g.
seasonal shutdown).
The wiring diagrams below are examples for a safe and reliable compressor wiring:
Wiring information
Control device .................................................. TH
Optional short cycle timer (3 min) ......... 180 s
Control relay .................................................... KA
Liquid Line Solenoid valve .........................LLSV
Compressor contactor .................................. KM
Phase monitor ................................................ PM
Safety lock out relay ........................................KS
Pump-down control low pressure switch ..LP
High pressure safety switch........................ HPs
Fused disconnect ............................................ Q1
Fuses ...................................................................F1
Compressor motor ...........................................M
Discharge gas thermostat ......................... DGT
M
DGT
HPs
180 s
TH
LP
CONTROL CIRCUIT
F1F1
KM
KM
KM
KA KA
A1
A2
A3
KA
KA
KS
KS
KS
L1 L3 L2
Q1
T1
T3
T2
LLSV KS
Wiring diagram with pump-down cycle
PM
Note:
For H-series compressor, phase monitors are mandatory. The selected phase monitor should lock out
the compressor from operation in reverse.