Brochure
29AB218186428184en-US1501
GENERAL INFORMATIONPRODUCT INFORMATIONINTEGRATION INTO SYSTEMORDERING INFORMATION SYSTEM DESIGN
Manage operating envelope
R
Requirement
The operating envelope for H-series scroll
compressors is given in the figures below and
guarantees reliable operations of the compressor
for steady-state and transient operation.
Steady-state operation envelope is valid for a
suction superheat within 9°F to 54°F range.
R22, R407C
Model variation T
68
77
86
95
104
113
122
131
140
149
158
-22 -13 -4 5 14 23 32 41 50 59
Evaporating temperature (°F)
Condensing temperature (°F)
SH 20°F
R410A
Model variation T
68
77
86
95
104
113
122
131
140
149
158
Evaporating temperature (°F)
Condensing temperature (°F)
SH 20°F
SH 9°F
HCJ121 & HCJ 120
condensing temperature boundary
-22 -13 -4 5 14 23 32 41 50 59