Brochure

21AB218186428184en-US1501
GENERAL INFORMATIONSYSTEM DESIGNINTEGRATION INTO SYSTEMORDERING INFORMATION PRODUCT INFORMATION
If start assist is required, in case of operating
below the nominal voltage, a CSR starting device
is required.
During start-up, the start winding (C-S) is
energised through an electromagnetic potential
relay and a start capacitor.
A permanent (run) capacitor is wired between
the start winding (C-S) and the run winding (C-R).
CSR wiring
Danfoss scroll compressors are designed to
operate without any assistance if running within
the defined nominal voltage. PSC wiring is
sufficient (see below).
The start winding (C-S) of the motor remains in
circuit through a permanent (run) capacitor.
This permanent (run) capacitor is connected
between the start winding (C-S) and the run
winding (C-R).
Electrical connections
PSC wiring
C
S
R
Line
Run
Capacitor
Start
Capacitor
Potential
Relay
1
2
5
C
S
R
Line
Run
Capacitor
Electrical data, connections and wiring
Nominal capacitor value
and relays
Models
PSC wiring
Run capacitor
CSR wiring
Start capacitor
Relay
50 Hz, motor voltage code 5
R22
HRM025-032-034-038-040-042 70 μF 145-175 μF 3ARR3*3AL* RVA 9CKL
HRM045-047 60 μF 145-175 μF 3ARR3*3AL* RVA 9CKL
HRM054 55 μF 161-193 μF 3ARR3*24AP* RVA 3EKL
HRM058-060 55 μF 88-108 μF 3ARR3*25AS* RVA 4GKL
HLM068-072-075-081 55 μF 88-108 μF 3ARR3*25AS* RVA 4GKL
R407C
HRP025-034-038-040-042 70 μF 145-175 μF 3ARR3*3AL* RVA 9CKL
HRP045-047 60 μF 145-175 μF 3ARR3*3AL* RVA 9CKL
HRP054 55 μF 161-193 μF 3ARR3*24AP* RVA 3EKL
HRP058-060 55 μF 88-108 μF 3ARR3*25AS* RVA 4GKL
HLP068-072-075-081 55 μF 88-108 μF 3ARR3*25AS* RVA 4GKL
R410A
HRH029-031-032-034-036 70 μF 145-175 μF 3ARR3*3AL* RVA 9CKL
HRH038-040 60 μF 145-175 μF 3ARR3*3AL* RVA 9CKL
HRH051-054-056 55 μF 88-108 μF 3ARR3*25AS* RVA 4GKL
HLH061-068, HLJ072-083 55 μF 88-108 μF 3ARR3*25AS* RVA 4GKL
60 Hz, motor voltage code 1
R22
HRM025-032-034 45 μF 145-175 μF 3ARR3*3M* RVA 2ACKL
HRM038 55 μF 88-108 μF 3ARR3*3L* RVA 2ABKL
HRM040-042-045-047 60 μF 88-108 μF 3ARR3*3L* RVA 2ABKL
HRM048 60 μF 161-193 μF 3ARR3*3L* RVA 2ABKL
HRM051-054 70 μF 161-193 μF 3ARR3*3L* RVA 2ABKL
HRM058T1-060T1 55 μF 88-108 μF 3ARR3*25S* RVA A4IKL
HRM058U1-060U1, HLM068-072-
075-081
80 μF 189-227 μF 3ARR3*3L* RVA 2ABKL
R407C
HRP051 70 μF 161-193 μF 3ARR3*3L* RVA 2ABKL
HLP068-072-075-081 80 μF 189-227 μF 3ARR3*3L* RVA 2ABKL
R410A
HRH031 45 μF 145-175 μF 3ARR3*3M* RVA 2ACKL
HRH032-034 50 μF 88-108 μF 3ARR3*3L* RVA 2ABKL
HRH036 55 μF 88-108 μF 3ARR3*3AL* RVA 9CKL
HRH038-039-040 60 μF 88-108 μF 3ARR3*3L* RVA 2ABKL
HRH041-044-048-049-050-051 70 μF 161-193 μF 3ARR3*3L* RVA 2ABKL
HRH054-056, HLH061-068, HLJ072-
083
80 μF 189-227 μF 3ARR3*3L* RVA 2ABKL
in reverse, but as a reverse rotation situation can
go unnoticed for longer periods, phase monitors
are recommended.
For HC* series compressors, phase monitors are
required. The selected phase monitor should
lock out the compressor from operation in
reverse.