Brochure

16 AB218186428184en-US1501
GENERAL INFORMATIONSYSTEM DESIGNINTEGRATION INTO SYSTEMORDERING INFORMATION PRODUCT INFORMATION
Three phase electrical
characteristics
Compressor model
LRA MCC Max. operating current Winding resistance (Ohm)
A A A L2-L3 L1-L3 L2-L1
Motor voltage code 2
200-220 V / 3 ph / 50 Hz
208-230 V / 3 ph / 60 Hz
HRM034U2 95 17.5 13.6 1.18 0.87 1.18
HRM038U2 95 19 14.8 1.18 0.87 1.18
HRM040U2 95 20 15.5 1.18 0.87 1.18
HRM042U2 95 22 16.6 1.18 0.87 1.18
HRM045U2 115 25 18.9 0.98 0.73 0.98
HRM047U2 115 25 20.1 0.98 0.73 0.98
HRM054U2 123 27 21.7 0.59 0.59 0.59
HRM058U2 123 27 22.7 0.59 0.59 0.59
HRM060U2 123 28 23.5 0.59 0.59 0.59
HLM068T2 170 30 26.6 0.48 0.48 0.46
HLM072T2 170 30 28.2 0.48 0.48 0.46
HLM075T2 190 35 31.6 0.42 0.42 0.42
HLM081T2 190 39 35.2 0.42 0.42 0.42
HCM094T2 190 40 36.1 0.37 0.37 0.37
HCM109T2 235 46 40.7 0.33 0.32 0.32
HCM120T2 250 55 47.6 0.30 0.29 0.29
Motor voltage code 4
380-415 V / 3ph / 50 Hz
460 V / 3 ph / 60 Hz
HRM025T4 30 7 4.9 6.72 4.95 6.72
HRM034T4 45 9.5 6.8 4.66 3.42 4.66
HRM034U4 45 9.5 6.8 4.66 3.42 4.66
HRM038T4 45 9.5 7.6 4.66 3.42 4.66
HRM038U4 45 10 7.2 4.66 3.42 4.66
HRM040U4 45 10 7.5 4.66 3.42 4.66
HRM042T4 45 11 8.3 4.66 3.42 4.66
HRM042U4 45 11 8.3 4.66 3.42 4.66
HRM045U4 50 12 8.9 3.87 2.85 3.87
HRM047T4 50 12 9.3 3.87 2.85 3.87
HRM047U4 50 12 9.3 3.87 2.85 3.87
HRM048U4 60 12.5 9.4 2.65 2.61 2.60
HRM051T4 60 13 9.8 2.65 2.62 2.60
HRM054T4 70 12.5 10.5 2.37 2.35 2.34
HRM054U4 70 13.1 11.0 2.37 2.35 2.34
HRM058U4 70 15 11.3 2.37 2.35 2.34
HRM060T4 70 15 11.7 2.37 2.36 2.35
HRM060U4 70 15 11.7 2.37 2.35 2.34
HLM068T4 82 15 12.4 1.80 1.88 1.87
HLM072T4 82 15 14.1 1.82 1.86 1.85
HLM075T4 100 16 15.0 1.70 1.68 1.69
HLM078T4 87 16 15.6 1.67 1.69 1.72
HLM081T4 87 17 16.6 1.82 1.82 1.83
HCM094T4 95 21 18.1 1.48 1.48 1.48
HCM109T4 110 24 20.3 1.30 1.28 1.34
HCM120T4 140 25 23.9 1.13 1.11 1.10
Motor voltage code 7
575 V / 3ph / 60 Hz
HRM038U7 38 8.5 6.2 7.34 5.38 7.34
HRM042U7 38 9 6.6 7.34 5.38 7.34
HRM045U7 40 9.5 7.1 6.09 4.47 6.09
HRM047U7 40 10 7.4 6.09 4.47 6.09
HRM054U7 53 11 8.4 4.12 4.06 4.03
HRM058U7 53 11.5 8.8 4.12 4.06 4.03
HRM060U7 53 11.5 9.1 4.04 3.97 3.94
HLM072T7 63.6 11.5 11.3 2.98 2.83 2.87
HLM075T7 72 13.5 11.8 2.51 2.48 2.53
HCM094T7 75 16 14.4 2.30 2.31 2.34
Motor voltage code 9
380 V / 3ph / 60 Hz
HRM034T9 52 12 8.3 3.01 2.20 3.01
HRM038T9 52 12 9.3 3.01 2.20 3.01
HRM042T9
52 12.5 10.1 3.01 2.20 3.01
HRM047T9 59.6 8.3 11.3 2.51 1.84 2.51
HRM054T9 81 16.5 12.7 1.49 1.46 1.48
HRM060T9 81 17 14.2 1.03 1.02 1.03
HLM072T9 96 20 17.0 1.27 1.25 1.28
HLM081T9 110 19 20.4 1.13 1.08 1.10
HCM094T9 135 25 21.9 0.93 0.91 0.93
HCM120T9 135 27 23.9 0.87 0.88 0.89
Motor voltage code 2
200-220 V / 3 ph / 50 Hz
208-230 V / 3 ph / 60 Hz
HRP025T2 14.5 9.6 1.67 1.23 1.67
HRP038T2 95 19 14.8 1.18 0.87 1.18
HRP040T2 95 20 15.5 1.18 0.87 1.18
HRP047T2 115 25 20.1 0.98 0.73 0.98
HRP051T2 120 26 20.1 0.68 0.67 0.67
HRP058T2 123 27 22.7 0.59 0.59 0.59
HRP060T2 123 28 23.5 0.59 0.59 0.59
HLP068T2 170 32 27.3 0.48 0.48 0.46
HLP072T2 170 33 28.2 0.48 0.48 0.46
HLP075T2 190 35 31.6 0.41 0.40 0.41
HLP078T2 190 37 33.4 0.43 0.43 0.44
HLP081T2 190 39 35.2 0.43 0.43 0.44
HCP094T2 190 40 36.1 0.37 0.37 0.37
HCP109T2 235 46 40.7 0.33 0.32 0.32
HCP120T2 250 55 47.6 0.30 0.29 0.29
Electrical data, connections and wiring