Application guidelines Danfoss scrolls, H-Series Residential and light commercial R22, R407C, R410A; 50 - 60 Hz http://danfoss.us.
Content GENERAL INFORMATION........................... 4 Manage operating envelope.................. 29 PRODUCT INFORMATION.......................... 5 Requirement.........................................................................29 R22, R407C Model variation T.........................................29 R410A Model variation T...................................................29 R22, R410A Model variation U........................................30 High and low pressure protection..................
General Information GENERAL INFORMATION Danfoss scroll compressors are designed and manufactured according to the state of the art and to valid European and US regulations. Particular emphasis has been placed on safety and reliability. Related instructions are highlighted with the following icons: This icon indicates instructions to avoid safety risk. ORDERING INFORMATION INTEGRATION INTO SYSTEM SYSTEM DESIGN PRODUCT INFORMATION R This icon indicates instructions to avoid reliability risk.
Features and process control were first priority. The result is a highly efficient product with the highest reliability obtainable, and a low sound level. The H-series compressors can be black or blue depending on the production site. GENERAL INFORMATION Danfoss H-series scroll compressors are manufactured using the most advanced machining, assembly, and process control techniques.
Compressor model designation GENERAL INFORMATION Danfoss H-series scroll compressor for R22/ R407C/R410A is available as single compressor and can be assembled in tandem combinations. The example below presents the compressor nomenclature which equals the technical reference as shown on the compressor nameplate. Code numbers for ordering are listed section “Ordering information and packaging”.
Technical specifications 50-60 Hz data Btu/h/W 10.9 10.7 11.2 10.7 11.1 11.1 11.2 10.8 11 11 11.5 11.4 11.5 11.8 11.5 11.6 11.5 11.5 11.5 11.7 11.7 11.6 11.7 11.7 10.9 10.9 11.4 11.2 11.2 11.2 11.4 11.2 11.3 11.1 11.5 11.5 11.6 11.9 11.5 11.6 11.5 11.6 11.6 11.7 11.7 11.7 11.7 11.7 Net Displacement Oil charge weight cu.
Technical specifications 50-60 Hz data GENERAL INFORMATION Model SYSTEM DESIGN PRODUCT INFORMATION 50Hz INTEGRATION INTO SYSTEM 60Hz HRP025T4 HRP034T4 HRP038T4 HRP040T4 HRP042T4 HRP045T4 HRP047T4 HRP048T4 HRP051T4 HRP054T4 HRP058T4 HRP060T4 HLP068T4 HLP072T4 HLP075T4 HLP081T4 HCP094T4 HCP109T4 HCP120T4 HRP025T4 HRP034T4 HRP038T4 HRP040T4 HRP042T4 HRP045T4 HRP047T4 HRP048T4 HRP051T4 HRP054T4 HRP058T4 HRP060T4 HLP068T4 HLP072T4 HLP075T4 HLP081T4 HCP094T4 HCP109T4 HCP120T4 Nominal tons Nominal cooling
Technical specifications 50-60 Hz data 60Hz W/W 2.93 2.82 2.79 2.93 2.82 2.76 2.85 2.93 2.76 2.93 2.99 3.05 3.02 3.02 3.11 3.21 3.21 3.22 3.25 3.18 3.23 3.22 2.99 2.99 3.02 2.99 2.99 2.93 3.02 2.99 3.02 2.99 3.08 3.14 3.11 3.11 3.17 3.2 3.19 3.25 3.22 3.24 3.28 3.25 Btu/h/W 10 9.62 9.51 10 9.62 9.41 9.72 10 9.41 10.01 10.22 10.42 10.32 10.31 10.61 10.96 11 11 11.1 10.87 11.01 11 10.2 10.2 10.3 10.2 10.2 10 10.3 10.2 10.3 10.2 10.5 10.7 10.6 10.6 10.8 10.9 10.9 11.1 11 11.07 11.18 11.08 Swept volume cu.
Dimensions GENERAL INFORMATION HRM025-032-034-038-040-042 / HRP025-034-038-040-042 / HRH029-031-032-034-036-038 / HRM-045-047 / HRP-045-047 / HRH039-040 9.40 7.491 - 7.509 4 x Ø 0.75 - 0.78 3.750 5.06 3.750 4.32 9.40 7.491 - 7.509 PRODUCT INFORMATION 4.38 14° 2.74 - 2.80 34° 31° 45° 6.438 - 6.515 Discharge line 0.502 - 0.506 SYSTEM DESIGN Suction line (1) 0.753 - 0.757 (2) 0.881 2.84 - 2.95 (1) 15.53 (2) 16.53 (1) 14.19 (2) 15.19 (1) 9.09 (2) 10.09 INTEGRATION INTO SYSTEM (1) 7.
Dimensions 9.41 7.491 - 7.509 9.41 7.491 - 7.509 4 x Ø 0.75 - 0.78 4 x Ø 0.75-0.78 3.750 3.750 3.750 5.44 5.26 4.66 3.750 4.69 9.41 9.41 (1) 4.76 (2) 4.8 14° 31° 14° 45° 45° Discharge line (1) 0.502-0.506 (2) 0.755 Suction line 0.878 - 0.885 2.84 - 2.95 SYSTEM DESIGN 7.187 - 7.265 7.187 - 7.265 Discharge line (1) 0.502-0.506 (2) 0.755 31° 34° 3.10 - 3.17 Suction line 0.878-0.885 3.63 - 3.70 17.16 15.85 15.85 17.16 10.27 10.27 INTEGRATION INTO SYSTEM 2.74-2.
Dimensions HCM/HCP 094-109-120 GENERAL INFORMATION 9.13 7.491 - 7.509 4 x Ø 0.75 - 0.78 3.750 3.750 5.24 9.13 4.93 7.491 - 7.509 PRODUCT INFORMATION 4.84 31° 34° 3.10-3.17 14° 45° 7.211 - 7.288 Discharge line 0.878-0.885 Suction line 1.128-1.135 SYSTEM DESIGN 3.63 - 3.70 (1) 19.29 (2) 19.67 (1) 20.35 (2) 20.72 13.79 INTEGRATION INTO SYSTEM 11.28 0.28 0.75 C6 (1) HCM/HCP 094 (2) HCM/HCP 109-120 All dimensions in inch ORDERING INFORMATION Terminal box Mounting grommet 0.
Dimensions GENERAL INFORMATION HCJ091-106-121 9.41 7.49 - 7.51 4 x Ø 0.75 - 0.78 3.75 5.24 3.75 4.93 9.41 7.49 - 7.51 PRODUCT INFORMATION PRODUCT INFORMATION 4.84 14° 3.10 - 3.16 34° 31° 45° 7.21 - 7.28 Discharge line 0.87 - 0.88 SYSTEM DESIGN Suction line 1.128 - 1.135 3.63 - 3.70 21.08 20.01 14.77 INTEGRATION INTO SYSTEM 12.26 0.43 HCJ091-106-121 All dimensions in inch Terminal box Mounting grommet 0.067 S T₂ 1.161 1.614 R T₃ Ø 0.
Dimensions GENERAL INFORMATION Gas equalization line Schrader ports for HP/LP switches and/or access ports H PRODUCT INFORMATION Oil equalization line Crankcase heaters W L 14 Tandems to be acheived by assembly of individual compressors, if they are the feature 8 compressor.
Electrical data, connections and wiring Motor voltage Danfoss scroll compressors H Series are available in four different motor voltages as listed below. Code 1 208-230 V - 1ph 187 - 253 V Code 2 200-220 V - 3 ph 180 - 242 V 208-230 V - 3 ph 187 - 253 V Code 4 380-415V - 3 ph 342 - 457 V 460 V - 3 ph 414 - 506 V Code 5 220-240 V -1 ph 198 - 264 V - Code 9 380 V - 3 ph 342 - 418 V to overheating and possible motor damage.
Electrical data, connections and wiring Motor voltage code 2 200-220 V / 3 ph / 50 Hz 208-230 V / 3 ph / 60 Hz Motor voltage code 4 380-415 V / 3ph / 50 Hz 460 V / 3 ph / 60 Hz Compressor model 16 AB218186428184en-US1501 575 V / 3ph / 60 Hz 380 V / 3ph / 60 Hz 200-220 V / 3 ph / 50 Hz 208-230 V / 3 ph / 60 Hz Motor voltage code 7 Motor voltage code 9 Motor voltage code 2 ORDERING INFORMATION INTEGRATION INTO SYSTEM SYSTEM DESIGN PRODUCT INFORMATION GENERAL INFORMATION Three phase electrical c
Electrical data, connections and wiring Winding resistance (Ohm) L2-L3 L1-L3 L2-L1 6.72 4.95 6.72 4.66 3.42 4.66 4.66 3.42 4.66 4.66 3.42 4.66 4.66 3.42 4.66 3.87 2.85 3.87 3.87 2.85 3.87 2.65 2.61 2.60 2.65 2.62 2.60 2.37 2.37 2.37 2.36 2.33 2.32 2.37 2.36 2.35 1.80 1.88 1.87 1.91 1.93 1.94 1.62 1.60 1.63 1.67 1.69 1.72 1.90 1.88 1.89 1.48 1.48 1.48 1.30 1.28 1.34 1.13 1.11 1.10 1.18 0.87 1.18 1.18 0.87 1.18 1.18 0.87 1.18 1.18 0.87 1.18 1.18 0.87 1.18 0.98 0.73 0.98 0.98 0.73 0.98 0.68 0.67 0.67 0.68 0.
Electrical data, connections and wiring 200-220 V / 1 ph / 50 Hz 208-230 V / 1 ph / 60 Hz Motor voltage code 5 AB218186428184en-US1501 HRH032U7 HRH034U7 HRH036U7 HRH038U7 HRH040U7 HRH041U7 HRH049U7 HRH051U7 HRH054U7 HRH056U7 HLH061T7 HLH068T7 HLJ072T7 HLJ083T7 HRH031U9 HRH034U9 HRH038U9 HRH054U9 HLH061T9 HLH068T9 HLJ072T9 HLJ083T9 Compressor model Motor voltage code 1 INTEGRATION INTO SYSTEM ORDERING INFORMATION 18 380 V / 3ph / 60 Hz Motor voltage code 9 PRODUCT INFORMATION SYSTEM DESIGN Single
Electrical data, connections and wiring 23 25 25 25 27 30 31.2 40 42 40 40 40 47 19 24.5 32.9 40 45 45 45 45 24 25 25 25.5 25.5 28 33 38 40 40 42 45 45 50 27 26.5 26 31 34 33 31 32 36.9 38 43 42 45 43 41 45 47 42 42 42 42 Winding resistance (Ohm) Start 1.51 1.51 1.51 1.51 1.51 1.61 1.61 1.02 1.02 1.02 1.02 1.02 1.02 1.74 1.57 1.47 0.86 1.76 0.84 0.84 0.84 1.51 1.51 1.51 1.51 1.51 1.61 1.61 1.02 1.02 1.02 1.02 1.02 1.02 1.02 1.45 1.57 1.66 1.40 1.22 1.21 1.19 1.31 0.86 0.86 1.06 1.06 0.84 1.06 0.84 0.84 0.
Electrical data, connections and wiring GENERAL INFORMATION IP rating The compressor terminal box IP rating according to IEC 529 is IP22 for all models. IP ratings is only valid when correctly sized cable glands of the IP rating is applied.
in reverse, but as a reverse rotation situation can go unnoticed for longer periods, phase monitors are recommended. For HC* series compressors, phase monitors are required. The selected phase monitor should lock out the compressor from operation in reverse. Electrical connections Danfoss scroll compressors are designed to operate without any assistance if running within the defined nominal voltage. PSC wiring is sufficient (see below).
Approvals and certifications GENERAL INFORMATION Approvals and certificates Danfoss scroll H-series compressors comply with the following approvals and certificates. Certificates are listed on the product datasheets: http://www.danfoss.
Operating conditions The compressor technology applied in Danfoss H-series scroll compressors in combination with PVE lubricant provides the best possible result in terms of reliability and compressor lifetime. The PVE lubricant is compatible with R22 which makes the Danfoss H-series scroll compressors a very versatile multi- refrigerant solution. Alkylbenzene oil Alkylbenzene oil can be applied in systems using HCFC refrigerants (R22).
Design piping General requirements Proper piping practices should be employed to: GENERAL INFORMATION 1. Ensure adequate oil return, even under minimum load conditions (refrigerant speed, piping slope). For validation tests see section “Manage oil in the circuit”. 2. Avoid condensed liquid refrigerant from draining back to the compressor when stopped (discharge piping upper loop). For validation tests see section “Manage off cycle migration”.
Danfoss scroll H series compressors in C8 version can be mounted in tandem assemblies. Such manifolding applications require special design considerations that go beyond the scope of this document. Please contact Danfoss for further information. By default, H series tandems are not factory-built, just provide tandem version compressors (feature 8). Connection Sizes Comp.1 Comp.
Design compressor mounting GENERAL INFORMATION General requirements Single requirements Compressors used in single applications must be mounted with flexible grommets. and the manifold assembly must be mounted with flexible grommets onto frame. Compressors used in parallel application must be mounted with rigid mounting spacers onto rails During operation, the maximum inclination from the vertical plane must not exceed 3 degrees.
The following sections focus on the causes and methods of mitigation for each of the above sources. For sound radiating from the compressors, the emission path is air and the sound waves are travelling directly from the machine in all directions.
Sound and vibration management GENERAL INFORMATION Mechanical vibrations Vibration isolation constitutes the primary method for controlling structural vibration. H-series scroll compressors are designed to produce minimal vibration during operations. The use of rubber isolators on the compressor base plate or on the frame of a manifolded unit is very effective in reducing vibration being transmitted from the compressor(s) to the unit. Rubber grommets are supplied with all H-series scroll compressors.
Manage operating envelope The operating envelope for H-series scroll R compressors is given in the figures below and guarantees reliable operations of the compressor for steady-state and transient operation. R22, R407C Model variation T Steady-state operation envelope is valid for a suction superheat within 9°F to 54°F range.
Manage operating envelope R22, R410A Model variation U 158 GENERAL INFORMATION 149 PRODUCT INFORMATION Condensing temperature (°F) 140 131 SH 20°F 122 113 104 95 86 77 68 -22 -13 -4 5 14 23 32 41 50 59 Evaporating temperature (°F) SYSTEM DESIGN Working pressure range high side R22 R407C R410A psi (g) 158-402 152-422 229-645 Working pressure range low side psi (g) 20-100 16-93 28-157 Maximum high pressure safety switch setting* psi (g) 421 435 653 Minimum low pressure sa
Manage operating envelope HP and LP must be monitored to respect operating envelope limitations.
GENERAL INFORMATION Manage superheat Requirement During normal operation, refrigerant enters the compressor as a superheated vapor. Liquid flood back occurs when a part of the refrigerant entering the compressor is still in liquid state. Liquid flood back can cause oil dilution and, in extreme situations lead to liquid slugging that can damage compression parts.
Manage superheat Test N° Purpose Test condition Pass criteria Solutions Liquid flood back testing must be carried out under expansion valve threshold operating conditions: a high pressure ratio and minimum evaporator load (A). Suction superheat >5K(9°F) 1. Check expansion valve selection and setting. 2. Add a suction accumulator*. Transient Tests must be carried out with most unfavorable conditions : • fan staging, • compressor staging •… Refer to flood back chart criteria 1.
PRODUCT INFORMATION GENERAL INFORMATION Manage off cycle migration R Off -cycle refrigerant migration happens: • when the compressor is located at the coldest part of the installation, refrigerant vapor condenses in the compressor. • or directly in liquid-phase by gravity or pressure difference. When the compressor restarts, the refrigerant diluted in the oil, or stored in evaporator, generates poor lubrication conditions and may reduce bearings life time.
Manage off cycle migration Test N° Migration test Purpose Check that there is no migration of refrigerant into the compressor (either liquid or vapour condensating) Test condition Energize CCH*. Stabilize the non-running system at a pressure equivalent to 41°F . Raise the system pressure equivalent to 68°F. When saturated condensing temperature reaches 68°F then start the unit.
Provide power supply and electrical protection GENERAL INFORMATION Wiring information “Electrical data, connections and wiring”) •H P safety switch and DGT must be wired in the safety chain. Other safety devices such as LP can be either hardware or software managed. •P rovide separate electrical supply for the heaters so that they remain energized even when the machine is out of service (e.g. seasonal shutdown).
Control logic Tripping conditions Value Re-start conditions Time Value Time Manual reset HP switch Immediate, no delay. No by- pass Conditions back to normal. Switch closed again Maximum 5 auto reset during a period of 12 hours, then manual reset. Contact M1-M2 opened Danfoss requires a minimum compressor running time of 2 minutes to ensure proper oil return and sufficient motor cooling. Additionally, compressor service life is based on a maximum of 12 starts per hour.
Control logic GENERAL INFORMATION Defrost logic recommendations 2. Transferring liquid refrigerant from one exchanger to the other one thanks to pressures. In reversible systems, the defrost logic can be worked out to limit liquid flood back effect by: 1. Running full load during defrost to share liquid refrigerant between all compressors. st to 4W p m ay all co EX ode Valv m e( pr ind V o .
Requirements H-series compressors are delivered with < 100 ppm moisture level. At the time of commissioning, system moisture content may be up to 100 ppm. During operation, the filter drier must reduce this to a level between 20 and 50 ppm. Solutions To achieve this requirement, a properly sized and type of drier is required. Important selection criteria’s include: • driers water content capacity, • system refrigeration capacity, • system refrigerant charge.
GENERAL INFORMATION Assembly line procedure Compressor storage Store the compressor not exposed to rain, corrosive or flammable atmosphere between -31°F and 158°F when charged with nitrogen and between -31°F and 131°F when charged with refrigerant. Compressor holding charge Each compressor is shipped with a nominal dry nitrogen holding charge between 4 and 10psi and is sealed with elastomer plugs.
Assembly line procedure Piping assembly Good practices for piping assembly is a pre-requisite to ensure compressor service life.
Assembly line procedure GENERAL INFORMATION Vacuum evacuation and moisture removal Requirements: • Never use the compressor to evacuate the system. • Connect a vacuum pump to both the LP and HP sides. • Evacuate the system to a pressure of 500 μm Hg (9.7 mpsi) absolute. Recommendations: • Energized heaters improve moisture removal. • Alternate vacuum phases and break vacuum with Nitrogen to improve moisture removal.
Commissioning • Crankcase heaters must be energized at least 8 hours in advance to remove refrigerant. • A quicker start-up is possible by “jogging” the compressor to evacuate refrigerant. Start the compressor for 1 second, then wait for 1 to 2 minutes. After 3 or 4 jogs the compressor can be started. This operation must be repeated for each compressor individually.
Dismantle and disposal ORDERING INFORMATION INTEGRATION INTO SYSTEM SYSTEM DESIGN PRODUCT INFORMATION GENERAL INFORMATION Danfoss recommends that compressors and compressor oil should be recycled by a suitable company at its site.
Ordering information and packaging Single pack GENERAL INFORMATION Packaging Compressors are packed individually in a cardboard box. They can be ordered in any quantity. Minimum ordering quantity = 1. As far as possible, Danfoss will ship the boxes on full pallets of 9 compressors according below table.
Ordering information and packaging GENERAL INFORMATION Compressor code numbers Danfoss H-series scroll compressors can be ordered in either industrial packs or in single packs. Please use the code numbers from below tables for ordering.
Ordering information and packaging HRM034 T T U T T U T T U U T T U U T T T T T T T T P P P P P P P P P P P C C P C C C C C C C C 6 6 6 6 6 6 6 6 6 6 6 8 6 6 6 8 6 6 8 6 6 6 HRM038 HRM042 HRM047 HRM051 HRM054 HRM058 HRM060 HLM072 HLM075 HLM081 HCM094 HCM109 HCM120 1 2 121L0928 121L1091 121L0948 121L1128 Code no.
Ordering information and packaging PRODUCT INFORMATION GENERAL INFORMATION R407C Single pack Model Variation Connections Features HRP025 T P 6 121L3086 HRP032 T P 6 121L3345 HRP034 T P 6 121L3092 121L3355 121L2024 121L3353 121L1086 121L1006 121L1096 121L1016 HRP038 T P 6 HRP040 T P 6 HRP042 T P 6 T P 6 HRP047 T P 6 HRP051 T P 6 121L1501 T P 6 121L3349 SYSTEM DESIGN HRP058 HRP060 HLP068 HLP072 INTEGRATION INTO SYSTEM HLP075 HLP078 HLP081 HCP081 HCP0
Ordering information and packaging Code no.
Ordering information and packaging PRODUCT INFORMATION GENERAL INFORMATION R410A Single pack Compressors Model Variation Connections Features HRH029 HRH032 HRH034 HRH036 HRH038 HRH040 U U U U U U U U U U U U U U U U U U U U T T T T T T T T T T T T T T T T T T T P P P P P P P C P C P P P C P P C C P C P C C C P C C P C C P C C C C C C C C 6 6 6 6 6 6 6 8 6 8 6 6 6 8 6 6 8 6 6 8 6 6 8 6 6 8 6 6 8 6 6 6 8 6 8 6 8 6 8 HRH041 HRH044 HRH047 HRH048 HRH049 HRH051 SYSTEM DESIGN HRH054 HRH056 HLH061 H
Ordering information and packaging HRH029 HRH032 HRH034 HRH036 HRH038 HRH040 U U U U U U U U U U U U U U U U U U U U T T T T T T T T T T T T T T T T T T T P P P P P P P C P C P P P C P P C C P C P C C C C P C C P C P C C C C C C C C 6 6 6 6 6 6 6 8 6 8 6 6 6 8 6 6 8 6 6 8 6 6 8 6 8 6 6 8 6 6 6 6 8 6 8 6 8 6 8 HRH041 HRH044 HRH047 HRH048 HRH049 HRH051 HRH054 HRH056 HRH061 HLH068 HLJ072 HLJ075 HLJ083 HCJ091 HCJ106 HCJ121 1 121L2274 121L1138 121L1143 121L1148 121L1153 121L1158 121L1278 121L1283 121L2
Spare parts & accessories GENERAL INFORMATION Run capacitors for PSC wiring PRODUCT INFORMATION Type Code n° Description Application Packaging Pack size 70 μF 120Z0051 PSC wiring Run Capacitor 70 μF, 50Hz,Motor Code 5: HRM025-042/HRP025-042/HRH029-036 60HZ,Motor Code 1 : HRM051-054/HRP051/HRH041-HRH051 Multipack 10 60 μF 120Z0050 PSC wiring Run Capacitor 60 μF, 50Hz,Motor Code 5: HRM045-047/HRP045-047/HRH038-040 60Hz,Motor Code 1 : HRM040-048/HRH038-HRH040 Multipack 10 55 μF 8173234 PSC
Spare parts & accessories Packaging Pack size 120Z0366 Rotolock adaptor (1-1/4" ~ 3/4") Group 1 suction Multipack 10 120Z0367 Rotolock adaptor (1-1/4" ~ 7/8") Group 2 & 3 suction Multipack 10 Group 4 suction Multipack 10 Code n° Description 120Z0364 Rotolock adaptor (1-3/4" ~ 1-1/8") Group 1 & 2 discharge Multipack 10 120Z0366 Rotolock adaptor (1-1/4" ~ 3/4") 120Z0365 Rotolock adaptor (1" ~ 1/2") Group 3 discharge Multipack 10 120Z0367 Rotolock adaptor (1-1/4" ~ 7/8") Group 4 disch
Spare parts & accessories GENERAL INFORMATION Mounting hardware PRODUCT INFORMATION Type Code No Description Application Packaging Pack Size 120Z5017 Mounting grommet All models Single pack 1 120Z5014 Mounting sleeve All models Single pack 1 120Z5031 Mounting kit, including 1 bolt, 1 sleeve, 1 washer All models Single pack 1 120Z5064 Mounting kit for 1 scroll compressor including 4 grommets, 4 sleeves, 4 bolts, 4 washers All models Single pack 1 Application Packaging Pack Siz
Danfoss Commercial Compressors is a worldwide manufacturer of compressors and condensing units for refrigeration and HVAC applications. With a wide range of high quality and innovative products we help your company to find the best possible energy efficient solution that respects the environment and reduces total life cycle costs.