Install Instructions
Table Of Contents
- 2. Menu Overview
- 3. Introduction
- 4. General Operation
- 5. Ground Fault Circuit Interrupter (GFCI) 1/2
- 5. Ground Fault Circuit Interrupter (GFCI) 2/2
- 6. Icons 1/2
- 6. Icons 2/2
- 7. Startup Wizard
- 8. Programed Heating Schedule
- 9. Operating Choices
- 10. Thermostat Setup Menu 
- 10.1 Heating Schedule 1/2 
- 10.1 Heating Schedule 2/2 
- 10.2 Energy Use 
- 10.3. User Settings 
- 10.4 Installer Settings 
- 10.4.1 Adaptive Function 
- 10.4.2 Open Window 
- 10.4.3 Sensor Application 1/2 
- 10.4.3 Sensor Application 2/2 
- 10.4.4 Sensor Type 1/2 
- 10.4.4 Sensor Type 2/2 
- 10.4.5 Floor Sensor Calibration 
- 10.4.6 Room Sensor Calibration 
- 10.4.7 Floor Protection 1/2 
- 10.4.7 Floor Protection 2/2 
- 10.4.8 Factory Reset 
- 10.5. WiFi Settings 1/3 
- 10.5. WiFi Settings 2/3 
- 10.5. WiFi Settings 3/3 
- 10.5 Weather Settings
- 11. Factory Settings
- 12. Troubleshooting 1/4
- 12. Troubleshooting 2/4
- 12. Troubleshooting 3/4
- 12. Troubleshooting 4/4
- 13. Contact
Floor limit temperatures are set under Menu/Installer Settings/Floor Protection.
Note that changes made under “Sensor Application” do not influence the “Floor
Protection” settings.
Maximum temperature depends on the floor type and temperature unit.
1. Tap the “Menu” button on the home screen.
2. Then tap the “Installer Settings” button to access the various installer settings.
3. Tap the “Sensor Application” button.
4. Tap the application that you want to use.
• Floor
• Room/Floor Protection
• Room
• Regulator
5. Confirm your choice with “√” or discard it with “X”.
The thermostat will automatically return to “Installer Settings”.
Note that, when changing Sensor Application, certain menu options may be grayed
out and inaccessible as they are not applicable with the current settings.