Article: 088L8067 Version: 01.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0 The factory settings are average values providing a relatively high degree of security and moderate energy consumption. Low security – lower energy consumption Conversely, low energy consumption and a moderate level of security against ice and snow could be prioritized.
Ground system When more than 1 area is controlled by the GX™ 850 system, it is also possible to prioritize the areas. Prioritizing makes it possible to operate 2 areas, even if the required power for 2 areas is not present. For more information about the ice and snow melting function of the GX™ 850, please refer to: Appendix B: “How it works”. At least 1 roof sensor is needed for each roof area, but for complex roof constructions, 2 or more sensors are recommended.
28 Post-heating If the reason for ending a heating period is a decrease of moisture to below the chosen level the post-heating period will start. Post-heating ensures that no ice and snow is left on the roof. Measuring temperature The heating function is suspended every third hour meaning that the heating cables are turned off. This is done in order to allow the sensors to measure the temperature, without being influenced by the heated cables. The temperature measurement may last up to 20 minutes.
B:Ground >>Melting A:Roof >>Standby ˜ A:Roof ÚStandby View alarm menu 5s 5s ¯ˆı View sensor measurements View and set operating mode View sensor measurements View and set operating mode B:Ground ÚMelting S ys tem B S ys tem A O nly vis ible when S ys tem B is ins talled ! Select system B: Ground Select system A: Roof ˜ ¯ˆı A:Roof B:Ground .
26 sensors found! No ground If no new s ens ors are found (E xample s howing ground s ys tem). Replace sensor: Sensor2 03FC24 Cancel replace sensor? Add sensor: ID: 03ABC1 Add sensor: ID: 03DEF1 Cancel add sensor? Sensor added! Sensor replaced! Cancel replace sensor? Add sensor: ID: 03DEF1 Replace sensor: Sensor1 03FB2F Add sensor: ID: 03ABC1 If new s ens or(s) found and pas s ive s ens or (s) found.
Installer menu Changing parameters and performance of systems System and sensor name It is possible to change the names of the system and connected sensors (see capital A: Installer menu. Clogged drain It is possible to enable and disable the “Clogged drain warning”. The factory setting is “Warning On”. Priority When using the GX™ 850 as a dual or combi system, it is possible to prioritize the systems. When the priority of 2 systems is equal, both systems can heat at the same time.
24 View sensor parameters View parameter Postheat = 1H View parameter Priority = 1 Leave this menu: Press Û Sensor1 Moist. lev. = 10 Sensor2 Temp. = 26.2≥C Sensor surface Temp. = 27.3≥C View parameter Stdb. T =-3.0≥C View parameter Melt. T= 4.0≥C View parameter Postheat = 1H View parameter Priority = 1 Sensor1 Moist. lev. = 10 Sensor2 Temp. = 26.2≥C Sensor2 Moist. lev. = 11 Leave this menu: Press Û Leave this menu: Press Û View parameter Moist. lev. = 50 Sensor1 Temp. = 26.
A typical ice and snow melting system consists of: • GX™ 850 • Only 1 GX™ 850 is allowed on the Devibus™ • Power supply • More power supplies can be connected in parallel (if needed) • Be aware of maximum number of sensors on each power supply (Refer to Technical Specification for power demand of sensors) • Ground and/or roof sensor(s) • Be aware of maximum number and cable length of sensors on each power supply (Refer to sensor manual for a more detailed description) Zone A is used for single system.
On Automatic Clogged drain System mode • Automatic • Constant ON (manual timer) • Manually OFF On/off 0 to 9 hours 32°F (0°C) to 50°F (10°C) 5 to 95 (5 being the most sensitive to moisture) Range/Options 22 Factory settings 50 27°F (-3.0°C) 39°F (4.
or wait… Config system: System A Checkingsystem <------> System A! Installed 1Roofsensor found. Accept? System type: Roof System A Scanning... Press 12 to end configuration. Press to end configuration. If for some reason you do not wish to configure the system now you can press skip configuration of system . Please refer to “Changing parameters and performance of systems” in “User Manual” for description of the configurable parameters. Press to configure System A.
20 If the user selected a new sensor to add, the sensor is added. Press when the correct new sensor to add is found or “Cancel add sensor?” is selected. Press to loop through the found new sensors or to cancel add sensor. Add an extra sensor: From the installer menu select Change system. The system is searching for connected sensors. Setup Instructions Sensor added! Cancel add sensor? Add sensor: ID: 03ABC1 Checkingsystem <------> or wait… Press to end configuration.
System type: Ground Select system type: Ground (if ground system is preferred as System B) Connectsensors: System B System B Scanning... or wait… System is being scanned to find type of connected sensors… Press If sensors for System B are not connected - do it now! System A! Installed 1Roofsensor found. Accept? Wait until correct number of sensors for System A is found.
to activate Change system. 18 If no new sensors are found, it is reported to the user. Message is shown for 3 seconds. If any passive sensors are found, they are reactivated. Message is shown for 3 seconds. The system is searching for connected sensors. Press From the installer menu select Change system. Reactivate passive sensors: The given example is for a ground system.
or wait… System B Scanning... System type: Ground System is being scanned to find type of connected sensors… Select system type 16 or wait… Connectsensors: SystemB Press Connect sensors for System B. System A Installed! 1Groundsensor found. Accept? Wait until correct number of sensors for System A is found. Press when all sensors for System A are found… System A is installed… System type: Ground System A Scanning...