Install Instructions
Settings
Function
Moisture level
Standby temperature
Melting temperature
Post-heat
Clogged drain
System mode
Factory settings
50
27 F (-3 C)
39
° °
°F (4°C)
1 hour
On
Automatic
Options
5 to 95 (5 being the most sensitive
to moisture)
- 4 (-20°F to 32°F °C to 0°C)
34°F to 50°F (1°C to 10°C)
0 to 9 hours
On/off
Automatic
Constant On (manual timer, 9H)
Manually Off
Settings
Function
Moisture level
Melting temperature
Post-heat
Clogged drain
System mode
Factory settings
50
35°F (1.5°C)
1 hour
On
Automatic
Options
5 to 95 (5 being the most sensitive
to moisture)
32°F to 50°F (0°C to 10°C)
0 to 9 hours
On/off
Automatic
Constant On (manual timer)
Manually Off
Ground Application
Roof Application
Part No.
Description
Voltage
Part Numbers
GX sensors
088L3051
Ground sensors (two per package)
088L3052
Roof sensor
GX accessories
GX controls
088L3405
Nameplate (per NEC 426-13)
Factory Settings
CD-ST
Presetting
2
CD-ST VD.33.U1.02 © Danfoss 06/99
Presetting
2
Copyright 2009 Danfoss Inc.
8
088L3411
088L3440
088L3441
088L3442
088L3443
088L3444
088L3445
088L3446
088L3447
GX 850 Automatic Control Panel (ACP)
GX Contactor Panel with 4hr timer
GX Contactor Panel without timer
GX Timer Panel with 4 hr timer
GX Timer Panel without timer
GX Contactor Panel with timer and GFEP, 100A
GX Contactor Panel with GFEP, 100A
GX Contactor Panel with timer and GFEP, 200A
GX Contactor Panel with GFEP, 200A
208V-600V
208V-600V
208V-600V
208V-600V
208V-600V
208V-600V
208V-600V
208V-600V
208V-600V
EFH.IM.GX850 - 11/2009