Brochure

Connection 120V
Phase - Black
Neutral - Blue
Ground - Shield
Danfoss LX Floor Heating System
CAUTION!
It is important that this equipment is installed only by qualified electricians who are familiar with the proper sizing,
installation, construction and operation of floor warming system and the hazards involved. The heating mat is designed for
under floor heating purposes only.
Connection 240V
Phase - Black
Phase - Blue
Ground - Shield
LX Mat Specifications
2
The installation shall be in accordance with the manufacturers instructions and national and local codes.
The installation shall be in accordance with Part 424-J, American National Standard Institute / National Fire
Protection Association (ANSI/NFPA70), National Electrical Code (NEC) and Canadian Electrical Code (CEC),
Part 1. Danfoss recommends GFCI for heating cable in normally wet areas (i.e. bathrooms, showers, kitchens).
Note!
Type:
Voltage:
Output:
Heating Element Size:
Cold Lead
Bending radius:
Wire insulation:
Casing:
Max. Allowable Temp.:
Min. Installation Temp.:
Twin conductor
120V, 240V
2
12W/sq.ft. (130 W/m )
Width: 2’
Length: Refer to product label
Height: approx 1/8” (4 mm)
10’ (3.0 m)
Minimum 3/4” (19 mm)
TM
FEP, Teflon
PVDF
212°F (100°C)
40°F (5°C)
WARNING:
Remember to measure resistance.
The resistance should be measured between the two conductors, blue and black. Compare the measured resistance to the resistance listed on
the product label (on the power lead).
Record the resistance on your warranty card.
Also, measure the resistance between the blue, black and shielding/ground wire. Both should read
infinity.
MONITOR YOUR INSTALLATION!
USE THE LITTLE BUZZER CONTINUITY
ALARM (PART#088L0028)
Little Buzzer
Note: Operating the 240V mat at 208V reduces power output to approximately 9W/sq.ft.
(25% reduction)
Copyright 2009 Danfoss Inc.
TEL: 866-676-8062. FAX: 905-285-2055
088L3380 - 06/09