Product Overview

Technical Data
Supply voltage 24 V (Class II (SELV)) and 230 V (3 A pre-fuse)
Max. inrush current 24 V: 350 mA, 230 V: 250 mA
Frequency 50-60 Hz
Running power consumption 2 W
Spindle travel time ~3 min.
Ambient temperature 0-60° C
Enclosure IP 41
Cable length 1200 mm
Combination overview for Danfoss thermal wax actuator and valves (V) or manifolds (M)
Valve/
manifold
RA-N
(V)
RTD-N
(V)
RA-C
(V)
RA-FN
(V)
RA-G
(V)
RTD-G
(V)
RAV-/8
(V)
VMT-8
(V)
RAVL-6
(V)
FHD
(M)
k
VS
(m³/H)
0.65 to
1.40
0.65 to
1.40
1.20 to
3.30
0.65 to
1.40
2.06 to
4.75
2.00 to
4.40
1.20 to
3.10
1.50 to
3.10
0.20 to
1.50
0.10 to
1.10
Max. Δ
(Bar)
0.6 0.6 0.6 0.6 0.2* 0.2* 0.8 0.8 0.6 0.6
Actuator
**
TWA-A TWA-D TWA-A TWA-A TWA-A TWA-D TWA-V TWA-V TWA-L TWA-A
* The RA-G/ RTD-G 25 valve has a max. Δp = 0.16 bar. Consult valve/manifold datasheets for further infor-
mation.
**If the actuator should be an 24 V or 230 V and normally open (NO) or normally closed (NC), depends
mainly of the application, control strategy and the controller connected to the actuator.
Electrical Connection
Blue Green
Brown Green
* 24 V Class II transformer (SELV)
** 230 V max. 3 A pre-fuse
X
Please note: All NC-versions are equipped with a red mounting split on the position indicator to secure
easy valve connection. When mounted this split must be removed for correct operation.
Data Sheet TWA Thermal Wax Actuator
2 VDSAP502 © Danfoss 11/2010 Danfoss Heating Solutions