Product Overview
Table Of Contents
© Danfoss | DCS | 2019.04
Data sheet | Superheat controller type EKE 1A, EKE 1B, EKE 1C
DKRCC.PD.RS0.A4.02 | 82
Group
Par. name
Unit
PNU
Par. scale
Default
Par. min.
Par. max.
Access
Locked by
mainswitch
EEPROM
Remark
Alarm conguration
Alarm and Errors
A100 Low Min S4 delay sec. 3081 1 60 0 1200 RW x
A101 Low Min S4 band K 3082 10 2 0 30 RW x
A001 Upper temperature
alarm
K 3083 10 5 0 40 RW x
A002 Lower temperature alarm K 3084 10 3 0 40 RW x
A003 Temperature alarm delay min. 3085 1 30 0 90 RW x
A034 Battery alarm 3086 1 0 0 1 RW x
0 = O | 1 = On
A103 MOP alarm delay sec. 3087 1 60 0 1200 RW x
A104 MOP alarm dierential K 3088 10 5 0 40 RW x
A105 LOP alarm delay sec. 3089 1 60 0 1200 RW x
A106 LOP alarm dierential K 3090 10 5 0 40 RW x
A107 Cond.temp alarm delay sec. 3091 1 120 0 1200 RW x
A113 Cond. temp. alarm
dierential
K 3092 10 5 0 40 RW x
A108 High SH alarm delay sec. 3093 1 600 0 1800 RW x
A109 High SH alarm
dierential
K 3094 10 5 0 40 RW x
A110 Low SH alarm delay sec. 3095 1 60 0 1200 RW x
A102 Low SH alarm dierential K 3096 10 3 0 40 RW x
A112 Lack of capacity alarm
delay
min. 3097 1 0 0 120 RW x
Display
MMIGRS2
O011 Language
3157 1 0 0 0 RW 0 = $ActiveLanguageList
K004 Login timeout
min. 3158 1 10 1 120 RW x
K006 Backlight timeout
min. 3159 1 2 0 120 RW x
O005 Password daily
3160 1 100 0 999 RW x
K002 Password service
3161 1 200 0 999 RW x
K003 Password commission
3162 1 300 0 999 RW x
K005 Contrast % 3163 1 40
0
100 RW
x
K001 Brightness % 3164 1 80
0
100 RW
x
R005 Display unit 3165 1 0
0
1 RW x 0 = METRIC | 1 = IMPERIAL
K010 Opening degree unit 3166 1 0 0 1 RW
x
0 = Percent | 1 = Step
Communication
CAN/MODBus
G001 Controller adr.
3167 1 1 1 127 RW
x
G003 CAN bus min. update
interval
sec.
3168 1 5 0 20 RW x
G004 Modbus min. update
interval
sec.
3169 1 5 0 60 RW x
G005 Modbus baudrate
3170 1 6 0 8 RW x
0 = 0 | 1 = 1200 | 2 = 2400 | 3 = 4800
| 4 = 9600 | 5 = 14400 | 6 = 19200 | 7
= 28800 | 8 = 38400
G008 Modbus mode 3171 1 1 0 2 RW x 0 = 8N1 | 1 = 8E1 | 2 = 8N2
G007 Modbus mapping 3172 1 0 0 1 RW x 0 = Operation | 1 = Setup
G002 CAN baudrate
3173 1 1 0 5 RW
x
0 = 20k | 1 = 50k | 2 = 125k | 3 =
250k | 4 = 500k | 5 = 1M
Signal sharing via BUS
G012 Signal sharing Pe 3174 1 0 0 1 RW x 0 = O | 1 = On
G013 Signal sharing Pc 3175 1 0 0 1 RW x 0 = O | 1 = On
G014 Signal sharing S3 3176 1 0 0 1 RW
x
0 = O | 1 = On