Product Overview

© Danfoss | DCS | 2019.04
Data sheet | Superheat controller type EKE 1A, EKE 1B, EKE 1C
DKRCC.PD.RS0.A4.02 | 78
Group
Par. name
Unit
PNU
Par. scale
Default
Par. min.
Par. max.
Access
Locked by
mainswitch
EEPROM
Remark
Reference
Refrigeration on/o
R012 Main switch 3001 1 0 0 1 RW x 0 = O | 1 = On
Application
conguration
R102 Operation mode 3002 1 0 0 1 RW 0 = SH control | 1 = Valve driver
R100 Compressor capacity % 4001 10 0 0 100 RW x x
R015 Sensor select 3004 1 0 0 1 RW 0 = S3 | 1 = S4
Temperature control
R014 Thermostatic mode 3005 1 0 0 2 RW 0 = Not Used | 1 = CutIn/CutOut |
2 = MTR
R101 Temperature setpoint °C 3006 1 3 -70 70 RW x
R001 Dierential K 3007 10 2 0.1 10 RW x
N100 MTR Tn 3015 1 1800 20 3600 RW x
N101 MTR Kp 3016 10 3 0.2 20 RW x
External reference
signal
R006 Ext. ref oset max. K 3008 10 0 0.0 50 RW x
R106 Ext. ref oset min. K 3009 10 0 -50 0 RW x
Sensor/transmitter
correction
R009 S2 Correction K 3010 10 0 -10 10 RW x
R010 S3 Correction K 3011 10 0 -10 10 RW x
R105 S4 Correction K 3012 10 0 -10 10 RW x
R107 Pe Correction barg 3013 10 0 -5 5 RW x
R108 Pc Correction barg 3014 10 0 -5 5 RW x
Valve conguration
Valve setup
I067 Valve conguration 3132 1 0 0 32 RW
0 = no valve | 1 = UserDef | 2 = ETS
12C | 3 = ETS 24C | 4 = ETS 25C | 5 =
ETS 50C | 6 = ETS 100C | 7 = ETS 6 | 8
= ETS 12.5 | 9 = ETS 25 | 10 = ETS 50
| 11 = ETS 100 | 12 = ETS 250 | 13 =
ETS 400 | 14 = KVS 2C | 15 = KVS 3C |
16 = KVS 5C | 17 = KVS 15 | 18 = KVS
42 | 19 = CCMT 0 | 20 = CCMT 1 | 21 =
CCMT 2 | 22 = CCMT 4 | 23 = CCMT 8
| 24 = CCMT 16 | 25 = CCMT 24 | 26 =
CCMT 30 | 27 = CCMT 42 | 28 = CCM
10 | 29 = CCM 20 | 30 = CCM 30 | 31
= CCM 40 | 32 = CTR 20
I027 Valve motor type 3133 1 0 0 1 RW x 0 = Unipolar | 1 = Bipolar
I028 Valve drive current mA 3134 1 10 10 1000 RW
x
I029 Valve step positioning 3135 1 0 0 2 RW
x
0 = Fullstep | 1 = Halfstep | 2 = Auto
I030 Valve total steps stp 3136 1 1 1 8000 RW
x
I031 Valve speed PPS 3137 1 10 10 400 RW
x
I032 Valve start speed % 3138 1 20 1 100 RW
x
I061 Valve emengency speed % 3139 1 100 50 200 RW
x
I062 Valve acceleration current % 3140 1 100 100 150 RW
x
I063 Valve acceleration time ms 3141 1 10 10 150 RW
x
I077 Valve holding current % 3142 1 0 0 300 RW
x
I064 Valve step mode 3143 1 3 0 4 RW
x
0 = Full | 1 = Half | 2 = 1/4 | 3 = 1/8
| 4 = 1/16
I065 Valve duty cycle % 3144 1 100 5 100 RW
x
I066 Minimum OD % 3145 1 0 0 100 RW
x
N032 Maximum OD % 3146 1 100 0 100 RW
x
I069 Valve OD during stop % 3147 1 0 0 100 RW x
I070 Start backlash % 3148 10 0 0 50 RW
x
I071 Compensation backlash % 3149 10 0 0 10 RW
x
I072 Overdrive % 3150 10 4 0 20 RW
x
I073 Overdrive enable OD % 3151 1 0 0 100 RW
x
I074 Overdrive block time min. 3152 1 10 0 1440 RW
x
I076 Valve excitation time
after stop
ms 3154 1 10 0 1000 RW
x
I078 Preset OD % 3155 10 50 0 100 RW
x
I068 Valve neutral zone % 3156 10 0.5 0 5 RW x
Appendix 9
Parameters List
Explanations
Parameter Name and abbreviation
PNU The Parameter Number
Note: this is equivalent to the MODBus register number (modbus address + 1)
R/W R means read only. RW means it can be changed
Locked by
mainswitch
If the parameter is cong locked it means that the value can only be changed when the main switch is OFF
Default The default value of the parameter (factory setting)
Par min./Par max. Parameter minimum and Parameter maximum range.
Par. Scale This shows the scaling factor of the value
*1) means that there is no scaling
*10) means that the read value is 10 times larger than the actual value
Warning:
In modbus
Values are read / written as
16 bit integer values without
decimals. The values may need
to scale as shown on the table.