Product Overview
Table Of Contents
© Danfoss | DCS | 2019.04
Data sheet | Superheat controller type EKE 1A, EKE 1B, EKE 1C
DKRCC.PD.RS0.A4.02 | 78
Group
Par. name
Unit
PNU
Par. scale
Default
Par. min.
Par. max.
Access
Locked by
mainswitch
EEPROM
Remark
Reference
Refrigeration on/o
R012 Main switch 3001 1 0 0 1 RW x 0 = O | 1 = On
Application
conguration
R102 Operation mode 3002 1 0 0 1 RW 0 = SH control | 1 = Valve driver
R100 Compressor capacity % 4001 10 0 0 100 RW x x
R015 Sensor select 3004 1 0 0 1 RW 0 = S3 | 1 = S4
Temperature control
R014 Thermostatic mode 3005 1 0 0 2 RW 0 = Not Used | 1 = CutIn/CutOut |
2 = MTR
R101 Temperature setpoint °C 3006 1 3 -70 70 RW x
R001 Dierential K 3007 10 2 0.1 10 RW x
N100 MTR Tn 3015 1 1800 20 3600 RW x
N101 MTR Kp 3016 10 3 0.2 20 RW x
External reference
signal
R006 Ext. ref oset max. K 3008 10 0 0.0 50 RW x
R106 Ext. ref oset min. K 3009 10 0 -50 0 RW x
Sensor/transmitter
correction
R009 S2 Correction K 3010 10 0 -10 10 RW x
R010 S3 Correction K 3011 10 0 -10 10 RW x
R105 S4 Correction K 3012 10 0 -10 10 RW x
R107 Pe Correction barg 3013 10 0 -5 5 RW x
R108 Pc Correction barg 3014 10 0 -5 5 RW x
Valve conguration
Valve setup
I067 Valve conguration 3132 1 0 0 32 RW
0 = no valve | 1 = UserDef | 2 = ETS
12C | 3 = ETS 24C | 4 = ETS 25C | 5 =
ETS 50C | 6 = ETS 100C | 7 = ETS 6 | 8
= ETS 12.5 | 9 = ETS 25 | 10 = ETS 50
| 11 = ETS 100 | 12 = ETS 250 | 13 =
ETS 400 | 14 = KVS 2C | 15 = KVS 3C |
16 = KVS 5C | 17 = KVS 15 | 18 = KVS
42 | 19 = CCMT 0 | 20 = CCMT 1 | 21 =
CCMT 2 | 22 = CCMT 4 | 23 = CCMT 8
| 24 = CCMT 16 | 25 = CCMT 24 | 26 =
CCMT 30 | 27 = CCMT 42 | 28 = CCM
10 | 29 = CCM 20 | 30 = CCM 30 | 31
= CCM 40 | 32 = CTR 20
I027 Valve motor type 3133 1 0 0 1 RW x 0 = Unipolar | 1 = Bipolar
I028 Valve drive current mA 3134 1 10 10 1000 RW
x
I029 Valve step positioning 3135 1 0 0 2 RW
x
0 = Fullstep | 1 = Halfstep | 2 = Auto
I030 Valve total steps stp 3136 1 1 1 8000 RW
x
I031 Valve speed PPS 3137 1 10 10 400 RW
x
I032 Valve start speed % 3138 1 20 1 100 RW
x
I061 Valve emengency speed % 3139 1 100 50 200 RW
x
I062 Valve acceleration current % 3140 1 100 100 150 RW
x
I063 Valve acceleration time ms 3141 1 10 10 150 RW
x
I077 Valve holding current % 3142 1 0 0 300 RW
x
I064 Valve step mode 3143 1 3 0 4 RW
x
0 = Full | 1 = Half | 2 = 1/4 | 3 = 1/8
| 4 = 1/16
I065 Valve duty cycle % 3144 1 100 5 100 RW
x
I066 Minimum OD % 3145 1 0 0 100 RW
x
N032 Maximum OD % 3146 1 100 0 100 RW
x
I069 Valve OD during stop % 3147 1 0 0 100 RW x
I070 Start backlash % 3148 10 0 0 50 RW
x
I071 Compensation backlash % 3149 10 0 0 10 RW
x
I072 Overdrive % 3150 10 4 0 20 RW
x
I073 Overdrive enable OD % 3151 1 0 0 100 RW
x
I074 Overdrive block time min. 3152 1 10 0 1440 RW
x
I076 Valve excitation time
after stop
ms 3154 1 10 0 1000 RW
x
I078 Preset OD % 3155 10 50 0 100 RW
x
I068 Valve neutral zone % 3156 10 0.5 0 5 RW x
Appendix 9
Parameters List
Explanations
Parameter Name and abbreviation
PNU The Parameter Number
Note: this is equivalent to the MODBus register number (modbus address + 1)
R/W R means read only. RW means it can be changed
Locked by
mainswitch
If the parameter is cong locked it means that the value can only be changed when the main switch is OFF
Default The default value of the parameter (factory setting)
Par min./Par max. Parameter minimum and Parameter maximum range.
Par. Scale This shows the scaling factor of the value
*1) means that there is no scaling
*10) means that the read value is 10 times larger than the actual value
Warning:
In modbus
Values are read / written as
16 bit integer values without
decimals. The values may need
to scale as shown on the table.