Product Overview

© Danfoss | DCS | 2019.04
Data sheet | Superheat controller type EKE 1A, EKE 1B, EKE 1C
DKRCC.PD.RS0.A4.02 | 67
ID Symptom Possible cause / Reaction Solution
6 High superheat Lack of sub-cooling. Limit max opening degree of the valve setting in controller.
Check refrigeration system capacity and compare with expansion
valve capacity. Use proper valve size suitable for the system.
Controller is not setup/tuned properly. Check the controller superheat settings SH min., max. and sensors
connected to it.
Tune PID parameters in the controller.
Wrong valve selected from the controller list or
undersized valve installed.
Check the right valve type and setting or use the appropriate valve
size for the needed condition.
Seasonally high load condition or overloaded
the system.
Check the heat exchanger for dirts.
Check superheat performance.
7 Too high or too low
measured superheat
Wrong sensor type, refrigerant type,
pressure transmitter type and/or range.
Check the related setting and range.
In case of oset in sensor or pressure transmitter, perform the
sensor correction.
Always use accurate pressure transmitter
8 a. Measured Superheat
is higher than reference
- more than 5K for
5 - 10 min.
Load condition has changed and the superheat
controller is too slow to adapt to the change.
TN can be adjusted to 20% lower and Kp can be adjusted to be
20% higher, monitor that the adjustment don’t make the valve OD
and Pe/Te oscillate.
Compressor capacity has changed and the
superheat controller is too slow to adapt to the
change.
Compensation for compressor change is done with KpTe in this
case KpTe can be adjusted to be 20% higher.
Missing valve capacity. Check if valve OD is close to 100 %, if so the valve is missing
capacity , check if sub cooling is OK.
System might have loss charge.
b. Measured Superheat
is lower than reference -
lower 3K
SH close parameter is disabled or not setup
optimally.
Enable the SH close function and set the setpoint 2K below the
reference.
Compressor capacity has changed and the
superheat controller is act too aggressive to
adapt to the change.
Compensation for compressor change is done with KpTe in this
case KpTe can be adjusted to be 20% lower.
9 Fluctuating superheat The S2 sensor not in good contact with the
suction line.
Check proper mounting of the temperature sensor.
Fast change in load and ambient condition. Wait for the stable condition and check again.
Periodic ash gas at the valve inlet. Secure stable sub cooling.
Aggressive gain Kp and Kp Te parameter. Decrease gain in the controller, ex set SH Tn to be 20 % higher and
reduce Kp 20%, if still SH is uctuating, reduce KpTe by 20%.
Try with the higher SH reference.
10 Negative superheat Wrong sensor type, refrigerant type, pressure
transmitter type and range.
Check the related setting and range.
During start up suction pressure is low
because of low Ambient temperature.
Check the startup problem.
System is not running. Check the system.
11 Superheat outside the
dened range or does
not reached the setpoint
Wrong valve selected or its valve parameter. Check the right valve type and its setting.
Loss of refrigerant in the system. Charge the system with appropriate refrigerant capacity.
Check for leakage in the system.
Expansion valve too small. Replace with larger valve if necessary.
Check the selected valve in the controller valve list.
Step loss in the valve. Drive the stepper valve with the recommended Speed.
Too high or too low speed could result in loss step in the valve.
For the user dened valves, check the other valve settings such as
current, duty cycle, holding current and other relevant parameter.
Use overdrive features to mitigate the loss steps. Use the correct
overdriving values with respect to the used value.
Wrong dened valve type or its setting.
Longer cables mounted than specied for the controller.
Separate Valve cable from other high power cables and do not
bundle the cables.
Blockage in the valve or high friction in the valve.
MOPD exceeded than specied in the valve specication.