ID Symptom Possible cause / Reaction Solution
1 Regulation does not
start on using control
modes i.e. MSS
DI is not connected, if dened as ON/OFF
hardware switch.
Turn on DI switch.
Sensor / transmitter error. Check and clear alarm.
Alarm conguration conict i.e. S2 sensor not
dened or no refrigerant selected.
Clear and clear Alarm.
Alarm: standby mode active i.e. Parameter
R012 is OFF.
Set R012 main switch to 1.
2 Suction pressure too low Pressure drop across evaporator too high. Check refrigerant ahead of expansion valve.
If valve is placed much higher than condenser outlet.
Check pressure dierence.
Lack of sub cooling ahead of expansion valve. Limit max opening degree of the valve setting in controller.
Check refrigeration system capacity and compare with expansion
valve capacity.
Use proper valve size.suitable for the system.
Evaporator superheat too high. Check the section “ High Superheat .
Pressure drop across the expansion valve less
than valve is sized for.
Check pressure drop across expansion valve.
Replace with larger valve.
Expansion valve too small. Check refrigeration system capacity and compare with expansion
valve capacity. Replace with larger valve if necessary.
Check selected valve type in the controller valve list.
Expansion valve block with foreign material. Remove valve and examine the orice /piston.
Wrong selection of Refrigerant in the controller
settings.
Choose the correct Refrigerant from the pre-dened list.
Lack of Charge in the system. Charge the system with appropriate refrigerant capacity.
Check for leakage in the system.
Pressure transmitter ranges or type is wrongly
dened.
Dene the correct pressure range.
MOP set point is dened very low. Check the MOP setting, if Modbus is used, check if the values have
been scaled as indicated in the parameter list.
Evaporator wholly or partly iced up. De-ice evaporator.
Low chilled water ow Check ow as per design
chilled water temp too low Check temp set points as per design
3 Low pressure cut out
due to compressor cut
in and cut out
Missing start signal. Check for digital input DI signal or its settings.
Startup problem. Check section start- up problem and its solution.
4 Liquid hammer in
compressor (noisy or
unusual compressor
sound) and /or frost on
the suction line
Superheat reference set too low. Increase the SH reference by changing the SH min. max. parameter.
Superheat is too low. Make sure SH Close function is ON.
Increase the values of SH close and SH min.
Also check section “Too low superheat”.
Inaccurate SH measurement or slow response
in S2 sensor.
Ensure that S2 sensor is secured on suction line.
Insulate temperature sensor properly.
Check the product installation guide section temperature sensor.
Refrigerant or pressure transmitter is not set
correctly.
Check the related parameters.
5 Too Low superheat Min. SH parameter is too low set. Raise the min. SH parameter.
Valve Cannot Close fully. Reduced the Valve OD or forced opening time at Start up.
Valve OD too large at start up. Use P-control.
Reduce Start OD.
Inaccurate superheat. Mounting position of Temperature sensor. Place sensor close to
evaporator.
High pressure drop in suction line. Mounting position of the pressure transmitter. Place the
transmitter close to evaporator.
Check the product installation guide section temperature sensor.
Valve is stuck at open. Check valve installation.
Liquid returns to compressor. Check section Liquid hammering.
27.0 Trouble shooting