Data sheet | Superheat controller type EKE 1A, EKE 1B, EKE 1C
DKRCC.PD.RS0.A4.02 | 62
Label Modbus
PNU
Bit
No.
Alarm Description Actions during
active
Trigger (how the alarm
is raised)
How to clear the alarm Remark
CONFIGURATION ERRORS
E101 1901 9 Conguration error Auto operation
blocked
Active when:
- DI2 and DI3 have
the same mapping
conguration.
- AI1 and AI5 have
the same mapping
conguration.
Correct application settings One or more conguration errors is blocking
operation to start. Check the other active
alarms to identify the conguration problem
E011 1901 1 No refrigerant
selected
Auto operation
blocked
O030 refrigerant set to
none
Set O030 refrigerant set to
an actual refrigerant
No refrigerant is selected, congure the correct
refrigerant. See "O030 Refrigerant"
E112 1903 12 AI5 not available on
this variant
Auto operation
blocked
Variant conict EKE 1A
has 1 temp. sensor
Change settings, so S3 and/
or S4 is not used
EKE 1A only operate with 1 temperature sensor
on AI2, please set I020 AI1 conguration = Not
used
E113 1903 13 AI3 not available on
this variant
Auto operation
blocked
Variant conict on
EKE 1A and And B
conguration problem
EKE 1C if PT1000
Set sensor for AI5 to be of
NTC 10K type
EKE 1A and EKE 1B don’t operate with 3
temperature sensors, please set I022 AI5
conguration = not used
E120 1903 4 AI1 not available on
this variant
Auto operation
blocked
Variant conict NO DI3
on EKE 1B and 1C
Set DI3 conguration to “not
used”
EKE 1B and EKE 1C only operate with 2 DI.
Please set O037 DI3 conguration = Not Used
E110 1903 10 Temp. oset is not
available on this
variant
Auto operation
blocked
Variant conict (not
possible to do temp
oset on EKE 1A)
Not set ext. ref conguration
to “v->temp” or “mA->t”
EKE 1A don’t include thermostat function.
Therefore, oset of temperature set point via
analogue signal is not possible. Don’t set O010
Ext. ref. conguration to mA->Temp or V->Temp
E111 1903 11 MODbus is not
available on this
variant
Auto operation
blocked
Variant conict (not
possible to use Modbus
on EKE 1A)
Not set ext. ref conguration
to “Modbus->temp” or
“Modbus->SH” or for valve
driver don’t set driver
reference conguration to
Modbus-> OD/steps
EKE 1A don’t include Modbus. Don’t set O010
Ext. ref. conguration to Modbus->SH or
Modbus->Temp
E104 1902 3 SH reference too
close to SH close
set point
Auto operation
blocked
SH close is used and SH
close set pint is too close
the actual reference/
reference minimum
Disable SH close or correct
the actual SH reference /
reference minimum to have
0,5K dierence to SH close
set point
SH reference can come to close to the SH close
safety functions et point, which can result in
unstable operation. Keep min. 0,5K separation
between minimum SH reference and N119 SH
close set point.
E105 1902 4 LOP set point too
close to MOP set
point
Auto operation
blocked
If MOP and LOP is used,
Mop set point - Lop set
point must > 5K
Disable MOP or LOP, or
adjust the dierence on
MOP-LOP set point >= 5K
The set point for the 2 pressure safety function
Lop and Mop is to close. Keep min. 5K
separation between N011 MOP set point and
N140 LOP set point
E129 1902 5 No sensor
congured for S4
Auto operation
blocked
Application need a
S4 signal for either
thermostat or Min
S4, but S4 signal is
congured
Disable the functions
needing S4 or congure a
S4 signal
Operation is congured to use S4 (media out)
sensor, but no S4 sensor is congured, Correct
I020 AI1 conguration or AI5 conguration and
check I042 S4 sensor conguration
E106 1902 6 No sensor
congured for S3
Auto operation
blocked
Thermostat need a S3
signal and no s3 signal is
congured
Disable the functions
needing S4 or congure a
S4 signal
Operation is congured to use S3 (media in)
sensor, but no S3 sensor is congured, Correct
I020 AI1 conguration or AI5 conguration and
check I041 S3 sensor conguration
E107 1902 7 SH min higher than
SH max
Auto operation
blocked
SH max lower than
SH low
Adjust SH max or SH low, SH
Max >=SH low
N010 SH min. is set higher than N009 SH max..
E108 1903 8 OD min higher than
OD max
Auto operation
blocked
OD max lower than
OD low
Adjust OD max or OD low,
OD Max >=OD low
I066 Minimum OD is set higher than N032
Maximum OD
E109 1903 9 No transmitter
congured for Pc
Auto operation
blocked
Application need
PC signal for
high condensing
temperature protection
Disable High condensing
temperature protection or
congure PC transmitter
Operation is congured to use Pc transmitter,
but no Pc transmitter is congured. Correct I022
AI4 conguration and check I044 Pc transmitter
conguration
E125 1903 4 AI5 can’t operate
with AKS sensor
Auto operation
blocked
ON EKE 1C AI5
conguration is setup as
AKS sensor
Set AI5 conguration to the
of NTC10K typew
EKE 1C don't support AKS sensor on AI5. Please
use a temperature sensor on NTC type on AI5.
Correct, I022 AI5 conguration
E132 1904 9 No sensor
congured for S2
Auto operation
blocked
S2 Sensor conguration
= Not dened
No sensor type dened for S2
E133 1904 10 No transmitter
congured for Pe
Auto operation
blocked
Pe transmitter
conguration =
Not dened
No pressure transmitter type dened for Pe
E134 1904 11 Ext. ref.
conguration error
Correct setting Check the ext. ref. signal and the ext. ref.
conguration.
26.0 Alarm and error table