Data sheet | Superheat controller type EKE 1A, EKE 1B, EKE 1C
DKRCC.PD.RS0.A4.02 | 49
18.0 SH or Temp
Reference via
External signal
Superheat reference or temperature reference can be oset by external analog signal.
SH reference is not allowed to oset the signal below SH min.
Parameter (R006 Ext. ref oset max. ,R106 Ext. ref oset min. ) dene the range of the oset,
parameter (I034, I035) and (I036, I037) dene the signal range of the external signal (default is
0-10 V and 4-20mA)
Note:
The curve can be dened
in reverse direction as well.
18.1 SH reference
Using the SH Reference via the analog input a displacement can be made of the temperature
reference or of the superheat reference. The signal can either be a current signal or voltage signal.
The reference can be displaced in positive or negative direction.
EKE 1A 1B 1C
Applicable
Parameter Function Description
O010 Ext ref. conguration
dene how the external refernce signal is used
7 = mA->SH: External current signal oset superheat reference
1 = V->SH: External voltage signal oset superheat reference
4 = Modbus - SH : Modbus give oset to superheat reference
I037 Ext ref. current high if O010=3, dene max. reference current
I036 Ext ref. current low if O010=3, dene min. reference current
I035 Ext ref. voltage high if O010=4, dene max. reference Voltage
I034 Ext ref voltage low if IO010=4, dene min. reference Voltage
X010 Bus ext. ref. if O010=5, readout oset in Kelvin
I037 Ext ref. current high if O010=3, dene max. reference current
I036 Ext ref. current low if O010=3, dene min. reference current
I035 Ext ref. voltage high if O010=4, dene max. reference Voltage
I034 Ext ref voltage low if IO010=4, dene min. reference Voltage
X010 Bus ext. ref. if O010=5, readout oset in Kelvin
Parameter Function Description
O010 Ext ref. conguration
dene how the external refernce signal is used
9 = mA->Temp: External current signal oset temperature reference
3 = V->Temp : External voltage signal oset temperature reference
6 = Modbus->T: Modbus give oset to temperature reference
18.2 Temperature reference
Temperature reference can be change as descripted above using either 0 – 20 mA signal or
4 – 20 mA signal.
The thermostat reference can be displaced via an external voltage signal which is particularly
useful for process cooling. The signal may be e.g 0 – 5 V or user dened voltage signal. Two
oset values must be set, one indicating the displacement at minimum signal and another
indicating the displacement at maximum signal. The displacement will apply to all sections.
The displacement will not aect the alarm limits.
EKE 1A 1B 1C
Applicable
-
Voltage
Offset
I035
Ext ref. voltage high
0
I034
Ext ref. voltage low
R006
Ext. ref offset max.
R106
Ext. ref offset min
10
5
Danfoss
80G354.10
Danfoss
80G356.10
Curren
t
Offset
I037
Ext ref. current high
I036
Ext ref. current low
R006
Ext. ref offset max
.
R106
Ext. ref offset min
4
20
4
-2