Product Overview

© Danfoss | DCS | 2019.04
Data sheet | Superheat controller type EKE 1A, EKE 1B, EKE 1C
DKRCC.PD.RS0.A4.02 | 37
13.0 EKE Application EKE serves 3 dierent main applications
• Driver Mode
• Controller Mode
- Superheat controller
- Temperature controller
• Service Mode
13.1 Driver Mode
A master is commanding the valve open degree to the EKE controller. The control signal can be:
Analog signal e.g. 0 – 10 V or 4 – 20 mA
Bus communication via RS485 (Modbus RTU)
'Normal closed' valve in front of EEV is optional alternative to a battery backup solution which closes
the EEV in case of power fail. The Digital output can also be used as alarm indication to the master
controller.
The Master can send a start signal to EKE DI terminals.
Danfoss
80G8221.01
EEV
TT
P
S2
Battery
Optional connection
Alarm indication
Normal close
Mandatory connection
ON/OFF signal
Modbus or Analog signal
Power 24 V AC / 24 V DC
EKE controller (in driver mode)
MASTER controller