Submittal Sheet

Data sheet Thermostatic expansion valves, type TUA/TUAE and TCAE
3DKRCC.PD.AG0.A4.22 / 520H8945
MOP-points
Refrigerant
Range N
-40 +50°F
Range NM
-40 − +25°F
Range B
-75 − -15°F
MOP point for evaporating temperature t
e
and evaporating pressure p
e
t
e
= +60°F t
e
= +32°F t
e
= -4°F
R22 p
e
= 100 psig p
e
= 60 psig p
e
= 20 psig
R134a p
e
= 55 psig p
e
= 30 psig
R404A / R507 p
e
= 120 psig p
e
= 75 psig p
e
= 30 psig
R407C p
e
= 95 psig p
e
= 50 psig p
e
= 20 psig
R410A p
e
= 165 psig p
e
= 100 psig p
e
= 45 psig
To avoid charge migration when using MOP
valves, the bulb temperature must always be
lower than the thermostatic element temperature.
Main valve data is indicated on the valve element
(g. 1), on the valve body (g. 2) and on the
bottom of the orice assembly (g. 3).
Example valve body
TUAE = Type (E = external equalization)
068U2214 = Code number
R134a = Refrigerant
MOP 55 / +15°C = MOP-point in psig / °C
40 /+10°C = Evaporating temperature
range in °C
40 /+50°F = Evaporating temperature
range in °F
PS 34bar/
MWP 500 psig = Max. working pressure in
bar/psig
N1810B = Date marking
(week 18, year 2010,
weekday B = Tuesday)
= Normal ow direction
in. = Connection in inches
Example orice assembly
TU = Valve type
5 = Orice number
068U1035 = Code no., orice assembly
incl. lter and gasket
1810 = Date marking
(Week 18. Year 2010)
Identication
Fig. 1 Power element
Fig. 2 Valve body
Fig. 3 Orice assembly
MOP valves