Submittal Sheet
Data sheet Thermostatic expansion valves, type TUA/TUAE and TCAE
3DKRCC.PD.AG0.A4.22 / 520H8945
MOP-points
Refrigerant
Range N
-40 − +50°F
Range NM
-40 − +25°F
Range B
-75 − -15°F
MOP point for evaporating temperature t
e
and evaporating pressure p
e
t
e
= +60°F t
e
= +32°F t
e
= -4°F
R22 p
e
= 100 psig p
e
= 60 psig p
e
= 20 psig
R134a p
e
= 55 psig p
e
= 30 psig
R404A / R507 p
e
= 120 psig p
e
= 75 psig p
e
= 30 psig
R407C p
e
= 95 psig p
e
= 50 psig p
e
= 20 psig
R410A p
e
= 165 psig p
e
= 100 psig p
e
= 45 psig
To avoid charge migration when using MOP
valves, the bulb temperature must always be
lower than the thermostatic element temperature.
Main valve data is indicated on the valve element
(g. 1), on the valve body (g. 2) and on the
bottom of the orice assembly (g. 3).
Example valve body
TUAE = Type (E = external equalization)
068U2214 = Code number
R134a = Refrigerant
MOP 55 / +15°C = MOP-point in psig / °C
−40 /+10°C = Evaporating temperature
range in °C
−40 /+50°F = Evaporating temperature
range in °F
PS 34bar/
MWP 500 psig = Max. working pressure in
bar/psig
N1810B = Date marking
(week 18, year 2010,
weekday B = Tuesday)
⇒ = Normal ow direction
in. = Connection in inches
Example orice assembly
TU = Valve type
5 = Orice number
068U1035 = Code no., orice assembly
incl. lter and gasket
1810 = Date marking
(Week 18. Year 2010)
Identication
Fig. 1 Power element
Fig. 2 Valve body
Fig. 3 Orice assembly
MOP valves