Submittal Sheet
Data sheet Thermostatic expansion valves, type TUA/TUAE and TCAE
2 DKRCC.PD.AG0.A4.22 / 520H8945
Product type Diagram
File name R64-1881
Date I.S.2008.03.14
Danfoss oers the following standard range of
thermostatic charges:
Range N -40 − 50 °F
Range N -40 − 50 °F, MOP 60 °F
Range NM -40 − 25 °F, MOP 32 °F
Range B
1
) -75 − -15 °F
Range B
1
) -75 − -15 °F, MOP -4 °F
Range F
2
) -40 − 50 °F MAH
1
) TU valves for range B are not supplied for R134a.
2
) See page 24.
Connection sizes Inlet x outlet:
1
/
4
in. x
3
/
8
in.
1
/
4
in. x
1
/
2
in.
3
/
8
in. x
1
/
2
in.
1
/
2
in. x
5
/
8
in.
External equalization:
1
/
4
in.
Static superheat (SS)
Valves without MOP
Electronic
thermostat
Thermostatic
expansion
valve
Solenoid
valve
Shut-o
ball valve
Sight glass
Shut-o
ball valve
Filter drier
Technical data
R134a, R22, R404A, R407A,
R407C, R407F, R410A:
9 °F
R507: 11 °F
Static superheat (SS)
Valves F-Range
R134a, R22/R407C, R407A, R407F :
3 °F
R407C: 1.1 °F
R507: 5.4 °F
Static superheat (SS)
Valves with MOP
R134a, R22, R404A, R407A,
R407C, R407F, R410A:
7 °F
R507: 9.5 °F
Capillary tube length: 59 inch.
Application example
Maximum bulb temperature: 212 °F
Maximum valve body temperature: 250 °F
Short-lived peak: 300 °F
Maximum working pressure
TUA/TUAE
MWP = 500 psig (R410A = 660 psig)
TCAE
MWP = 660 psig
Maximum test pressure
TUA/TUAE
p´= 540 psig (R410A = 725 psig)
TCAE
p´= 725 psig
Standard refrigerants
R22, R134a, R404A, R407A, R407C, R407F, R507
and R410A
Biow operation
With ow in the opposite direction, the rated
capacity is reduced by up to 15 %.
TUAE with orice 0 and 9, TCAE with orice 3, all
TUA and valves with MOP charges cannot be used
for biow operation.
TU and TC valves are continually evaluated for use
with newer refrigerants.
For further information, please contact Danfoss.