Technical Bulletin
Capacity in kW. Range: -60°C – -25°C.
Opening superheat sh = 4 K SI units R22
Valve
type
Orice
no.
Cond.
temp.
[°C]
Evap. temp. [°C]
-60 -50 -40 -30 -25
TE 5
0.5 40
2.72 3.82 5.16 6.70 7.53
01 40 4.92 6.96 9.45 12.3 13.9
02 40 6.76 9.66 13.2 17.3 19.5
03 40 8.31 11.9 16.5 21.7 24.5
04 40 10.5 15.3 21.6 29.1 33.1
TE 12
05 40 11.8 16.5 22.5 29.7 33.6
06 40
14.8 21.0 29.1 39.1 44.6
07 40 18.6 26.4 36.8 49.6 56.8
TE 55
9B 40
28.6 39.8 53.2 68.0 75.3
10 40 32.3 45.8 62.7 82.7 93.5
11 40
35.3 50.1 68.7 90.8 103
12 40 37.5 53.3 73.4 97.5 111
13 40 44.2 63.3 88.0 118 135
Capacity in TR. Range: -75°F – -15°F.
Opening superheat sh = 7.2 °F. US units R22
Valve
type
Orice
no.
Cond.
temp.
[°F]
Evap. temp. [°F]
-75 -60 -45 -30 -15
TE 5
0.5 105 0.79 1.05 1.35 1.70 2.09
01 105 1.43 1.90 2.48 3.13 3.84
02 105 1.96 2.64 3.46 4.39 5.41
03 105 2.41 3.26 4.29 5.48 6.79
04 105
3.03 4.17 5.60 7.29 9.16
TE 12
05 105 3.40 4.51 5.87 7.48 9.29
06 105
4.26 5.73 7.56 9.76 12.3
07 105
5.35 7.19 9.51 12.3 15.6
TE 55
9B 105 8.26 10.9 14.0 17.4 20.9
10 105
9.33 12.5 16.3 20.8 25.8
11 105 10.2 13.6 17.9 22.8 28.3
12 105 10.8 14.5 19.0 24.4 30.5
13 105 12.7 17.2 22.8 29.4 37.0
Capacity in kW. Range: -60°C – -25°C.
Opening superheat sh = 4 K SI units R22
Valve
type
Orice
no.
Cond.
temp.
[°C]
Evap. temp. [°C]
-60 -50 -40 -30 -25
TE 5
0.5 50 2.71 3.81 5.17 6.75 7.62
01 50 4.87 6.91 9.44 12.4 14.0
02 50 6.65 9.55 13.2 17.5 19.8
03 50 8.08 11.7 16.2 21.6 24.6
04 50
9.94 14.7 21.0 28.8 33.0
TE 12
05 50
11.2 15.8 21.7 29.0 33.0
06 50
13.8 19.8 27.7 37.6 43.3
07 50
17.0 24.3 34.2 46.6 53.7
TE 55
9B 50 26.9 37.6 50.6 65.4 73.0
10 50 29.6 42.1 58.1 77.4 88.0
11 50 32.0 45.7 63.2 84.3 95.9
12 50 33.7 48.2 66.9 89.7 102
13 50 38.8 56.1 78.6 107 122
Capacity in TR. Range: -75°F – -15°F.
Opening superheat sh = 7.2 °F. US units R22
Valve
type
Orice
no.
Cond.
temp.
[°F]
Evap. temp. [°F]
-75 -60 -45 -30 -15
TE 5
0.5 125 0.78 1.04 1.35 1.71 2.11
01 125 1.41 1.89 2.46 3.13 3.88
02 125
1.92 2.60 3.43 4.40 5.47
03 125
2.33 3.17 4.20 5.42 6.79
04 125 2.86 3.97 5.39 7.11 9.08
TE 12
05 125 3.21 4.29 5.62 7.22 9.05
06 125 3.96 5.35 7.12 9.28 11.8
07 125 4.83 6.54 8.72 11.4 14.6
TE 55
9B 125 7.68 10.2 13.2 16.5 20.1
10 125 8.42 11.3 14.9 19.2 24.0
11 125 9.12 12.3 16.2 20.8 26.1
12 125 9.57 12.9 17.1 22.1 27.8
13 125 11.0 15.0 20.0 26.0 33.1
Subcooling correction factor, f
sub
Subcooling [K] 2 4 10 15 20 25 30
Correction factor
0.98 1.00 1.05 1.10 1.14 1.19 1.23
Distributer correction factor, f
p
SI units R22
Pressure drop
[bar]
∆p
Evap. temp. [°C]
-60 -50 -40 -30 -25
Correction factor
0
1 1 1 1 1
1
0.96 0.96 0.96 0.95 0.95
1.5
0.94 0.93 0.93 0.93 0.93
2
0.91 0.91 0.91 0.90 0.90
Calculated at 32 °C condensing temperature.
Distributer correction factor, f
p
US units R22
Pressure drop
[psi]
∆p
Evap. temp. [°F]
-75 -60 -45 -30 -15
Correction factor
0
1 1 1 1 1
15
0.96 0.96 0.95 0.95 0.95
25
0.93 0.93 0.92 0.92 0.92
30
0.91 0.91 0.91 0.90 0.90
Calculated at 90 °F condensing temperature.
Subcooling correction factor, f
sub
Subcooling [°F] 2 7 10 20 30 40 50
Correction factor
0.97 1.00 1.02 1.07 1.12 1.17 1.22
Data sheet | Thermostatic expansion valves, type TE 5 – TE 55
© Danfoss | DCS (sw) | 2019.01
DKRCC.PD.AB0.A7.02 | 27