Technical Bulletin
Capacity in kW. Range: -60°C – -25°C.
Opening superheat sh = 4 K SI units R22
Valve
type
Orice
no.
Cond.
temp.
[°C]
Evap. temp. [°C]
-60 -50 -40 -30 -25
TE 5
0.5 20
2.63 3.66 4.87 6.18 6.84
01 20 4.80 6.71 8.95 11.4 12.6
02 20 6.68 9.38 12.6 15.9 17.6
03 20 8.39 11.9 15.9 20.3 22.5
04 20 11.0 15.7 21.4 27.6 30.6
TE 12
05 20 12.2 16.9 22.5 28.8 32.0
06 20
15.9 22.1 29.9 38.7 43.3
07 20 20.8 29.0 39.2 51.1 57.3
TE 55
9B 20
30.7 41.9 54.5 67.2 72.9
10 20 36.3 50.4 67.5 86.3 95.7
11 20
40.6 55.9 74.9 95.9 106
12 20 43.3 60.4 81.4 104 117
13 20 53.1 74.6 101 131 147
Subcooling correction factor, f
sub
Subcooling [K] 2 4 10 15 20 25 30
Correction factor
0.98 1.00 1.05 1.10 1.14 1.19 1.23
Capacity in TR. Range: -75°F – -15°F.
Opening superheat sh = 7.2 °F. US units R22
Valve
type
Orice
no.
Cond.
temp.
[°F]
Evap. temp. [°F]
-75 -60 -45 -30 -15
TE 5
0.5 65 0.76 1.00 1.27 1.57 1.88
01 65 1.38 1.83 2.34 2.89 3.45
02 65 1.93 2.56 3.28 4.06 4.82
03 65 2.43 3.23 4.16 5.17 6.18
04 65
3.19 4.29 5.58 7.00 8.41
TE 12
05 65 3.53 4.61 5.89 7.31 8.80
06 65
4.60 6.06 7.81 9.80 11.9
07 65
6.04 7.96 10.3 12.9 15.8
TE 55
9B 65 8.89 11.5 14.4 17.4 20.2
10 65
10.6 13.9 17.8 22.1 26.5
11 65 11.7 15.4 19.7 24.6 29.5
12 65 12.6 16.7 21.4 26.8 32.3
13 65 15.5 20.6 26.7 33.6 40.7
Distributer correction factor, f
p
SI units R22
Pressure drop
[bar]
∆p
Evap. temp. [°C]
-60 -50 -40 -30 -25
Correction factor
0
1 1 1 1 1
1
0.96 0.96 0.96 0.95 0.95
1.5
0.94 0.93 0.93 0.93 0.93
2
0.91 0.91 0.91 0.90 0.90
Calculated at 32 °C condensing temperature.
Distributer correction factor, f
p
US units R22
Pressure drop
[psi]
∆p
Evap. temp. [°F]
-75 -60 -45 -30 -15
Correction factor
0
1 1 1 1 1
15
0.96 0.96 0.95 0.95 0.95
25
0.93 0.93 0.92 0.92 0.92
30
0.91 0.91 0.91 0.90 0.90
Calculated at 90 °F condensing temperature.
Subcooling correction factor, f
sub
Subcooling [°F] 2 7 10 20 30 40 50
Correction factor
0.97 1.00 1.02 1.07 1.12 1.17 1.22
Capacity in kW. Range: -60°C – -25°C.
Opening superheat sh = 4 K SI units R22
Valve
type
Orice
no.
Cond.
temp.
[°C]
Evap. temp. [°C]
-60 -50 -40 -30 -25
TE 5
0.5 30 2.70 3.78 5.07 6.52 7.28
01 30 4.90 6.90 9.30 12.0 13.4
02 30 6.78 9.61 13.0 16.8 18.8
03 30 8.43 12.0 16.4 21.3 23.8
04 30
10.8 15.7 21.8 28.8 32.4
TE 12
05 30
12.1 16.9 22.8 29.7 33.4
06 30
15.6 21.8 29.9 39.5 44.8
07 30
19.9 28.0 38.6 51.2 58.1
TE 55
9B 30 30.0 41.3 54.6 68.7 75.5
10 30 34.7 48.7 66.0 86.0 96.4
11 30 38.1 53.6 72.8 95.0 107
12 30 40.8 57.5 78.5 103 116
13 30 49.1 69.7 95.9 127 143
Capacity in TR. Range: -75°F – -15°F.
Opening superheat sh = 7.2 °F. US units R22
Valve
type
Orice
no.
Cond.
temp.
[°F]
Evap. temp. [°F]
-75 -60 -45 -30 -15
TE 5
0.5 85 0.78 1.03 1.33 1.66 2.01
01 85 1.42 1.89 2.44 3.05 3.71
02 85
1.96 2.63 3.41 4.29 5.20
03 85
2.44 3.29 4.29 5.41 6.60
04 85 3.15 4.29 5.68 7.27 8.95
TE 12
05 85 3.51 4.63 5.98 7.53 9.23
06 85 4.49 5.98 7.82 9.97 12.4
07 85 5.77 7.69 10.1 12.9 16.1
TE 55
9B 85 8.69 11.4 14.4 17.7 21.0
10 85 10.1 13.4 17.3 21.9 26.8
11 85 11.1 14.7 19.1 24.2 29.6
12 85 11.9 15.8 20.6 26.1 32.1
13 85 14.3 19.2 25.1 32.1 39.8
Data sheet | Thermostatic expansion valves, type TE 5 – TE 55
© Danfoss | DCS (sw) | 2019.01
DKRCC.PD.AB0.A7.02 | 26