Product Overview
VDBJB122 © Danfoss 05/09
Data sheet VMT
2-Way Water Valve
Application:
Ordering
Information:
The VMT is a 2-way valve used in controlling the
flow of hot water within heating applications.
The VMT valve can be installed in applications
involving heating or chilled coils, hot water
storage tank, plate heat exchanger or floor
heating system. In the control of the VMT valve,
a thermostatic operator type RAVV or RAVK or
a 24VAC electric actuator type TWA-V or ABV
can be mounted to the valve to regulate the
temperature and flow through the valve. The
VMT valves are available in 1/2”, 3/4”, and 1” sizes
and the connections available are female solder
unions for 1/2” and 3/4” and male threaded
unions for 1”.
Features:
Seated valve
•
Brass body•
Low and high flow capacities•
1/2” and 3/4” double solder union•
Male NPT unions•
VMT Valves with Union Connections
Code No. Type Size Cv Connection
065F0102 VMT 15/8 1/2” 1.6 F. Solder Union
065F0104 VMT 20/8 3/4” 2.7 F. Solder Union
High Capacity, VMT Valves with Union Connections
Code No. Type Size Cv Connection
065F8960 VMT 15/2 1/2” 3.3 F. Solder Union
065F8961 VMT 20/2 3/4” 5.9 F. Solder Union
065F1242 VMT 25/2 1” 9.4 M. NPT Union
Suitable Thermostatic Operators
Code No. Type Setting Range Capillary Tube Length
013U1251
RAVV
104 – 158°F (40 - 70°C)
4’ 11” (1.5m)013U1252 80 – 132°F (27 - 56°C)
013U1255 50 – 100°F (10 - 38°C)
013U8063 RAVK 77 – 149°F (25 - 65°C) 6’ 5” (2m)
017-4370 1/2” Brass Sensor Well for RAVV or RAVK
Electric Actuators
Code No. Type Valve Function Supply Voltage
Power
Consumption
088H3120
TWA-V*
Normally closed
24 VAC
2.0 VA
088H3121 Normally open
082F0052
ABV
Normally closed
9.0 VA
082F0002 Normally open
*TWA-V should only to be used with VMT 15/8 and VMT 20/8 valves