Product Overview
© Danfoss | DCS (rm) | 2019.09
Data sheet | Heavy duty pressure switch, type MBC 5000 and MBC 5100
IC.PD.P10.4A.02 | 2
Technical data
Mechanical characteristics
Pressure connection
Standard G
¼
female (ISO 228-1) or flange
Option See specification form, page 4
Electrical connection Plug DIN 43650, Pg 9 / Pg 11 / Pg 13.5
Wetted parts material
Housing
Anodized AIMgSi1, AW-6082T6
Stainless steel 1.4306 (18/8),
acc. to EN10088-3
Bellows
Stainless steel 1.4306 (18/8),
acc. to EN10088-2
Diaphragm FKM
Piston
Stainless steel 1.4028 (3H13),
acc. to EN10088-2
O-ring NBR
Hole plug
(flange version)
Nickel plated brass or zinc plated
steel
Seal (piston version) Turcon T05
Enclosure material
Housing Anodized AIMgSi1, AW-6082T6
Plug fixture Glass filled polyamid, PA 6.6
Contact system Silver (AG) microprofile
Net weight 0.25 kg
Performance
Repeatability
Bellows versions
± 0.2 % FS (typ.)
± 0.5 % FS (max.)
Diaphragm versions
± 0.5 % FS (typ.)
± 1.0 % FS (max.)
Piston versions
± 1.0 % FS (typ.)
± 1.0 % FS (max.)
Max. switch frequency 10/min (0.16 Hz)
Differential See page 4
Permissible operating pressure See page 4
Burst pressure See page 4
Life time
Mechanical for diaphragm and bellows
Mechanical for piston type
Electrical at max. contact load
> 400,000 cycles
>1 million cycles
> 100,000 cycles
Environmental conditions
Temperature
Operation
Bellows versions
Diaphragm versions
Piston versions
-40 – 85 °C
-10 – 85 °C
-40 – 85 °C
Transport
Bellows versions
Diaphragm versions
Piston versions
-50 – 85 °C
-50 – 85 °C
-40 – 85 °C
Enclosure IP65, EN 60529
Vibration stability Sinusoidal
20 g, 25 – 2 kHz EN 60068-2-6
Piston type 4.4 g,
25 – 200 Hz
IEC 60068-2-27
Electrical specifications
Switch SPDT
Contact load
AC 15 0.5 A, 250 V
DC 13 12 W, 125 V