User Guide
4
3
2
5
6
M
I
N
Scale Plate
Cover
Mounting Hole
Capillary Tube
Conduit Rubber
Grounding Screw
Terminal Screw
DIFF.
Di. Adjusting
Knob
1.7
0.63 0.59
0.14
0.27
4.48
2.4
0.19
0.55
2.12
Danfoss
060L2101
0.88
remote bulb air coil/room sensor
Danfoss
060L2107
remote bulb
air coil/room sensor
Danfoss
060L2107
remote bulb air coil/room sensor
Danfoss
060L2107
remote bulb air coil/room sensor
Danfoss
060L2107
Installation guide
Thermostat
Type KPU
DKRCC.PI.CA0.F1.22 / 520H10107 1
060R9771
060R9771
Application
KPU 19 thermostats are used
for temperature regulation
in refrigeration, freezing, air
conditioning, ventilating and heating
systems.
KPU 19 thermostats are tted with
Single-Pole Double-Throw (SPDT)
or Single-Pole Single-Throw (SPST)
contact system.
The standard KPU 19 enclosure is rated
NEMA ~ 1.
NEMA ~ 1 is obtained when the
thermostat is mounted on a at
surface with all unused holes covered.
Type Regulating
range
[°F]
Dierential
∆T [°F]
Bulb size
[in.]
Capillary tube
length
[in.]
Max. bulb
temperature
[°F]
Ambient
temperature
[°F]
Contact
type
Reset
type
Code no.
KPU 19 -30 – 80 3.6 – 12.6
3
/
8
x 4
1
/
2
120 140
-31 – 158
SPDT Auto. 060L2150
KPU 19 -30 – 80 3.6 – 12.6
3
/
8
x 4
1
/
2
80 140
-31 – 158
SPST
(close on
temp. rise)
Auto. 060L2151
KPU 19 -30 – 80 3.6 – 12.6 -
Air coil / Room
sensor
140
-31 – 140
SPDT Auto. 060L2152
Product specication
Important
The KPU 19 thermostat is designed
only for use as a temperature
regulating operating control. It is the
responsibility of the installer to verify
that other necessary safety controls
are installed and functioning properly
as intended by the original equipment
manufacturer or system design.
Thermostat bulb types
Dimensions [in.]