Product Overview
Table Of Contents
Functions
Figure 1: Electrical diagram
Danfoss
60B55.13
If there is no oil pressure on starting, or if the oil pressure falls below the set pressure during operation, the
compressor will stop after the release time has elapsed.
The electrical circuit is divided into two completely separate circuits: a safety circuit and an operational circuit.
The timer (e) in the safety circuit is activated when the eective lubricating oil pressure, the oil dierential pressure
(the dierence between the oil pump pressure and suction pressure), is lower than the set value.
The timer is deactivated when the oil dierential pressure is more than the set value plus the contact dierential.
Figure 2: Functions for During start
Danfoss
60B59.13
On start-up
The two diagrams below explain the terms "oil dierential pressure" and "contact dierential". Both have to be
considered when using oil dierential pressure switches.
The rst diagram shows the function of the dierential switch during start; the second shows the function of the
switch during operation.
Pos. A: Normal start-up
The lubricating oil pressure is built up during start to the set/xed dierential plus the contact dierential, before
the timer cuts out (in this example, after 45 seconds).
At point A contacts T1-T2 open and timer (e) is stopped, i.e. normal lubricating oil conditions for the compressor
have been established.
Pos. B: The lubricating oil pressure does not reach the set/xed dierential plus the contact dierential before the
timer period elapses. At point B the timer cuts out operational circuit L-M and the compressor stops. If a signal
source is connected to terminal S, it will be activated. Restart can only be performed after about 2 minutes by
activation of the reset button, provided the cause of the fault has been determined.
Dierential pressure switch, Type MP 54, 55 and 55A
© Danfoss | Climate Solutions | 2021.02 AI211986438834en-000901 | 2