Adsorption charge
Bellows
Capillary tube
Sensor
that have been created as the result of cut-in action. These design features ensure that the cut-out point of the KP
switch remains very accurate and completely independent of the magnitude of the current load.
FLA - Motor Full Load Amperes
FLA is the largest current that a motor or other device is designed to carry at rated voltage and other specic
conditions. Also often called current at rated conditions.
LRA - Locked Rotor Amperes
LRA is the current in amperes drawn by an electric motor with the shaft or rotor immobilized.
Thermostats
Dierential
The dierential is the dierence between the cut-in and cut-out temperatures.
The dierential is necessary for satisfactory automatic operation of the controlled system. Mechanical dierential
(intrinsic dierential). The mechanical dierential is the dierential set by the dierential spindle.
Reset:
Manual reset: Units with manual reset can only be restarted after activation of the reset button. On max reset
units the set value is equal to cut-out value for rising temperature.
Automatic reset: Units with automatic reset is restored to operational mode automatically.
Snap function
A specic contact force is maintained until snap is initiated. The time over which contact force reaches zero is a few
milliseconds; therefore, contact bounce cannot occur as a result, for example, of slight vibrations before cut-out. The
snap-action contact system will continue to function even when micro-welds are created between the contacts
during cut-in. The force created to separate the contacts is strong, and instantly shears o all contact surface welds
that have been created as the result of cut-in action. These design features ensure that the cut-out point of the KP
switch remains very accurate and completely independent of the magnitude of the current load.
FLA - Motor Full Load Amperes
FLA is the largest current that a motor or other device is designed to carry at rated voltage and other specic
conditions. Also often called current at rated conditions.
LRA - Locked Rotor Amperes
LRA is the current in amperes drawn by an electric motor with the shaft or rotor immobilized.
Thermostat charge
Figure 1: Thermostat charge
Sensors with adsorption charges contain a superheated gas together with a solid having a large adsorption surface.
The sensor can be placed in zones that are warmer or colder than the switch housing and capillary tube, but
variations of more than 70 °F may inuence scale accuracy.