Data sheet | Pressure switch, KP
DKRCC.PD.CD0.1A.02 | 520H11562 | 7
KP 7BS
Design
(continued)
Types KP1, KP1A, KP2, KP6, KP6A, KP7 and KP17
units with designation W, B or S have been tested
and approved by TÜV, Rheinland in accordance
with EN 12263.
Types KP6, KP6A, KP7 and KP17 have a double
bellows: an outer bellows and a regulating
bellows. When system pressure exceeds the set
value, the KP will automatically stop the plant.
The double bellows system prevents loss of
charge in the event of bellows rupture.
A rupture in the inner bellows will cause the
control cut-out pressure to fall about 3 times less
the set value, thus the refrigeration plant
compressor will stop.
A rupture in the outer bellows will cause the
control cut-out pressure to fall to about 3 bar
under the set value, thus providing a fail-safe
function.
1. Pressure setting spindle
2. Dierential setting spindle
3. Main arm
15. Cable entry
18. Locking plate
25. Int. reset arm
30. Ext. reset button
KP 7W, are KP 7W, solder
Versions with designation W or AW cut in again
automatically when the pressure has fallen to the
set value minus the dierential.
Versions with designation B or AB can be cut in
manually with the external reset button when
the pressure in KP1 has increased 0.7 bar above
set value and in KP6 and KP7 has fallen 4 bar
under the set value.
Versions with designation S or AS can be cut in
manually with the internal reset arm when the
pressure has fallen 4 bar under the set value.
All KP pressure switches, including those which
are PED-approved, operate independently of
changes in the ambient temperature around the
control housing. Therefore the set cut-out
pressure and dierential are held constant
provided the permissible ambient temperatures
are not exceeded.