Product Overview

Data sheet | Pressure switch, KP
DKRCC.PD.CD0.1A.02 | 520H11562 | 4
For R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R438A, R448A, R449A, R450A, R452A, R507A, R513A
For complete list of approved refrigerants, visit www.products.danfoss.com and search for individual code numbers, where refrigerants are
listed as part of technical data.
Pressure Type
Low pressure (LP) High pressure (HP) Reset
Contact system
Code no.
Connection
Regulating
range
[bar]
Dierential
∆p
[bar]
Regulating
range
[bar]
Dierential
∆p
[bar]
Low
pressure
LP
High
pressure
HP
1
/
4
in.
6 mm
are
1
/
4
in.
ODF
solder
6 mm
ODF
solder
Low KP 1 -0.2 – 7.5 0.7 – 4.0 Auto SPDT 060 -110166
1
)
4
) 0 60 -11126 6
4
) 06 0 -111066
4
)
Low KP 1 -0.2 – 7.5 0.7 – 4.0 Auto SPDT 060 -11416 6
2
)
4
)
Low KP 1 -0.9 – 7.0 0.7
Man.
(Min.)
SPDT 06 0 -11036 6
1
) 06 0 -111166 06 0 -1109 66
Low KP 2 -0.2 – 5.0 0.5 – 1.5 Auto SPDT 060-112066
1
)
4
) 06 0 -112366
4
)
High KP 5 8 – 32 1.8 – 6.0 Auto SPDT 06 0 -117166
1
)
4
) 060 -117966
4
) 06 0 -117766
4
)
High KP 5 8 – 32 3
Man.
(Max.)
SPDT 060 -117366
1
) 060-118066
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Auto SPDT + LP signal 060-124166
4
) 060 -125466
4
)
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto
Man.
(Max.)
SPDT + LP signal 060 -124366
1
)
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto
Man.
(Max.)
SPDT + LP signal 060 -114 866
2
)
Dual KP 15 -0.9 – 7.0 0.7 8 – 32 4
Man.
(Min.)
Man.
(Max.)
SPDT + LP signal 060 -124566
1
)
Dual KP 15 -0.9 – 7.0 0.7 8 – 32 4 Conv.
3
) Conv.
3
) SPDT + LP signal 060-126166
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Auto
SPDT + LP and
HP signal
060-126566
1
)
4
) 060-129966
4
)
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto
Man.
(Max.)
SPDT + LP and
HP signal
060-126466
1
) 060-128466
1
)
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Conv.
3
) Conv.
3
)
SPDT + LP and
HP signal
06 0 -115466
4
) 060-001066
4
)
Dual KP 15 -0.9 – 7.0 0.7 8 – 32 4 Conv.
3
) Conv.
3
)
SPDT + LP and
HP signal
060-122066
Ordering
For R717, R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R438A, R448A, R449A, R450A, R452A, R507A, R513A
For complete list of approved refrigerants, visit www.products.danfoss.com and search for individual code numbers, where refrigerants are
listed as part of technical data.
Pressure Type
Low pressure (LP) High pressure (HP) Reset
Contact system
Code no.
Connection
Regulating
range
Dierential
∆p
Regulating
range
Dierential
∆p
Low
pressure
High
pressure
M10 × 0.75
1 m cap.
tube with
M10 × 0.75
[bar] [bar] [bar] [bar] LP HP
Low KP 1A -0.2 – 7.5 0.7 – 4.0 Auto SPDT 060 -116266
1
) 060-116066
4
)
Low KP 1A -0.9 – 7.0 0.7 Man. (Min.) SPDT 060-116166
High KP 5A 8 – 32 1.8 – 6.0 Auto SPDT 060-123066
4
)
High KP 5A 8 – 32 3 Man. (Max.) SPDT 060 -115366
1
) 060-123166
Dual KP 15A -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Auto
SPDT + LP and
HP signal
060-129566 060-129366
4
)
Dual KP 15A -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Man. (Max.)
SPDT + LP and
HP signal
060-129666 060-129466
Dual KP 15A -0.9 – 7.0 0.7 8 – 32 4 Conv.
3
) Conv.
3
) SPDT + LP signal 060-128366
1
) Available in Asia market with code 060-xxxx91
2
) Pressure switches with gold-plated contacts
3
) Conv.: optional automatic or manual reset
4
) Enclosure IP44
© Danfoss | DCS (rm) | 2019.03