Product Overview
Data sheet | Pressure switch, KP
DKRCC.PD.CD0.1A.02 | 520H11562 | 2
Technical data
Ambient temperature -40 – 65 °C (80 °C for max. 2 hours).
Ambient temperature (PED approved units) -25 – 65 °C (80 °C for max. 2 hours).
Media temperature *)
-50 – 100 °C
Max. working pressure
LP: PS / MWP = 17 bar
HP: PS / MWP = 35 bar
KP 6: PS / MWP = 46.5 bar
Max. test pressure
LP: P
e
= 20 bar
HP: P
e
= 35 bar
KP 6: P
e
= 46.5 bar
Contact load
Alternating current
AC1 =16 A, 400 V
AC3 = 16 A, 400 V
AC15 = 10 A, 400 V
Direct current DC13 = 12 W, 220 V control current
Wire dimensions
solid / stranded 0.75 – 2.5 mm
2
flexible, without ferrules 0.7 – 2.5 mm
2
flexible, with ferrules 0.5 – 1.5 mm
2
Tightening torque max. 2 Nm
Rated impulse voltage 4 kV
Pollution degree 3
Short circuit protection, fuse 16 A
Insulation 400 V
Enclosure IP30 / IP44 / IP55
*) The media temperature can be out of ambient temperature range under necessary condition that temperature inside KP must
be kept in ambient temperature range.
Contact systems
Low pressure (LP) High pressure (HP)
Dual pressure (LP/HP) Dual pressure (LP/HP) Dual pressure (HP/HP)
SPDT+LP signal SPDT+LP+HP signal
SPST
SPDTSPDT
© Danfoss | DCS (rm) | 2019.03