Test pressure
The test pressure is the pressure used in strength tests and / or leakage tests on refrigerating systems or individual
parts in systems. The test pressure is designated Pe.
“Snap function”
A certain contact force is maintained until irrevocable “snap” is initiated. The time during which the contact force
approaches zero is thus limited to a very few milliseconds. Therefore contact bounce cannot occur as a result of, for
example, slight vibrations, before the cut-out point. Contact systems with “Snap function” will change over even
when micro-welds are created between the contacts during cut-in. A very high force is created during cut-out to
separate the contacts. This force immediately shears o all the welds. Thus the cut-out point of the unit remains very
accurate and completely independent of the magnitude of the current load.
Setting
Pressure switches with automatic reset – LP: Set the LP start pressure on the “CUT-IN” scale (range scale). One
rotation of the low pressure spindle ~10 psi. Set the LP dierential on the “DIFF” scale. One rotation of the
dierential spindle ~ 3 psi. The LP cut-out pressure is the LP cut-in pressure minus the dierential.
NOTE:
The LP cut-out pressure must be above absolute vacuum pe = 30 in Hg. If compressor will not stop at low cut-out
pressure, check whether the dierential value is set at too high a value!
Metric conversions 1 psi = 0.07 bar
Pressure switches with automatic reset – HP: Set the HP cut-out pressure on the “CUT-OUT” scale. One rotation of
the HP spindle ~ 33 psi. Set the HP dierential on the “DIFF” scale.
One rotation of the dierential spindle ~ 4 psi. The HP cut-in pressure is the HP cut-out pressure minus the
dierential. Pressure switches with manual reset. Set the cut-out pressure on “CUT-OUT” scale (range scale). Low
pressure controls can be manually reset when the pressure is equal to the cut-out pressure plus the dierential.
High pressure switches can be manually reset when the pressure is equal to the cut-out pressure minus the
dierential.
Cut-in and cut-out pressures for both the LP and HP sides of the system should always be checked with an accurate
pressure gauge.