Submittal Sheet

Table Of Contents
KP 7W (KP 7B), are
KP 7W (KP 7B), capillary tube
KP 17W (KP 17B), are
Pressure setting spindle, (LP)
Dierential setting spindle
Main arm
Pressure setting spindle, (HP)
Cable entry
Locking plate
The KP with designations W or B have been tested and approved by TÜV (Germany) in accordance with EN 12263.
Versions with designation W will cut in automatically when the pressure has fallen to the setpoint minus the
dierential.
Versions with designation B can be cut in manually using the external reset button when:
KP 1 – the pressure has increased to 10 psi above the setpoint.
KP 7 – the pressure has fallen 58 psi below the setpoint.
KP 7 and KP 17 are equipped with fail-safe double bellows; a regulation bellows and an outer bellows. The double
bellows system protects against loss of system charge in the event of a bellows rupture.
A rupture in the outer bellows will cause the control to trip approximately 43 psi lower than the actual control
setting. This features provides a warning without a loss of charge.
All KP pressure switches, including those which are PED-approved, operate independently of changes in the
ambient temperature around the control housing. Therefore the set cut-out pressure and dierential are kept
constant provided the permissible ambient temperatures are not exceeded.
Terminology
Reset
1.Manual reset: Units with manual reset can only be reset during operation by activation of the reset button.
2.Automatic reset: After operational stop, these units reset automatically.
Maximum working pressure
The Maximum working pressure is determined by the pressure that can be safely allowed in the refrigerating system
or any of the units within it. The maximum working pressure is designated MWP.
© Danfoss | Climate Solutions | 2021.02 AI216886432258en-001101 | 5
Pressure switch, Type KP