Install Instructions
CAUTION:
The mounting panel must be plane to avoid damage of control.
Installation guide
Pressure switch
KP 1, KP 2, KP 5, KP 7W, KP 7B
060R9 746
060R9 746
© Danfoss | DCS (jmn) | 2016.10
DKRCC.PI.C00.E3.22 | 520H11541 | 1
Auto reset:
KP 1, KP 2, KP 5, KP 7W
Manual reset:
KP 1, KP 5, KP 7B
Mounting
CAUTION:
Do not mount the control in a position where dirt,
sediment or oil will aect the operation of the control.
CAUTION:
Do not install these controls on ammonia systems.
t
1
min. KP 1, KP 2, KP 5: -40 °F (-40 °C)
t
1
min. KP 7: -13 °F (-25 °C)
t
1
max.: 149 °F (65 °C)
Test pressure (P
test
)
Enclosure
max. ⁄ in
(3 mm)
B: Enclosure: ~NEMA 1
A: 10 – 32 UNC Threads
Connections
P
test
max.:
KP 1, KP 2: 285 psig (20 bar p
e
)
KP 5, KP 7: 510 psig (35 bar p
e
)
KP 2: 174 psig (12 bar p
e
)
Refrigerants:
R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R448A,
R449A, R450A, R452A, R507A, R513A
For complete list of approved refrigerants, go to
http://products.danfoss.com/all-products/
Mounting requirements Ambient temperatures