Submittal Sheet
© Danfoss | DCS (rm) | 2019.12 IC.PD.P10.F9.02 | 8
Data sheet | Pressure switch and Thermostat, KP and KPI
Technical data Dual pressure switch
Ambient temperature [°C] - 40 – 65 °C (for max. 2 hours up to 80 °C)
Media temperature [°C] Max. 100 °C
Fluid Liquids
Parts in contact with fluid
Bellows Phosphor bronze, CuSn6
Pressure connector Free-cutting steel (nickel plated)
Contact system
Contact load, Silver
Alternating current:
AC-1: 16 A, 400 V
AC-3: 16 A, 400 V
AC-15: 10 A, 400 V
Direct current:
DC-13: 12 W, 220 V
IP level IP22
Cable entry Rubber cable gland entry for 6 – 14 mm diameter cables
Mounted on backplate or wall bracket Vibration-proof in the range 0 – 1000 Hz, 4 g [1 g = 9.81 m/s
2
Mounting on angle bracket Not recommended for areas where vibration occurs
Pressure switch, type KP 44
Pressure range Differential Permissible
operating
pressure p
e
Max. test
pressure
Pressure
connection
Contact
material
Code no.Control Safety Control Safety
[bar] [bar] [bar] [bar] [bar] [bar]
2.0 – 12.0 0.5 – 6.0 0.7 – 4.0 1.0
Left side: 17
Right side: 17
Left side: 25
Right side: 19
2 × G
1
⁄4 A silver 060-001366
Ordering
left
side
right
side
manual