Technical data
Ambient temperature [°C] - 40 – 65 °C (for max. 2 hours up to 80 °C)
Sensor material Tinned copper Cu/Sn5
Contact system
Single-pole double throw (SPDT)
Contact load, Silver
Alternating current:
AC-1: 16 A, 400 V
AC-3: 16 A, 400 V
AC-15: 10 A, 400 V
Direct current:
DC-13: 12 W, 220 V
Contact load,
Gold plated contact set
See Information page 15
Enclosure, IP30 grade
Unit must be mounted on a flat surface / a flat fitting
and all unused holes covered
Enclosure, IP44 grade Mounted as IP30 plus fitting of top cover, code no. 060-109766
Enclosure, IP55 grade
Unit mounted in a special IP55 enclosure, code no. 060-033066
or 060-062866. Exception: KP 75
Cable entry Entry for 6 – 14 mm diameter cable
Mounted on backplate or wall bracket Vibration-proof in the range 0 – 1000 Hz, 4 g [1 g = 9.81 m/s
2
Mounted on angle bracket Not recommended for areas where vibration occurs
Thermostat, types KP 75 – KP 81
Type
Setting range Differential
Max. sensor
temperature
Capillary
tube length
Contact
material
Code no.
[°C] [°C] [°C] [m]
KP 75
0 – 40 3 – 10 80 Room sensor silver 060L121266
0 – 40 3 – 10 80 Room sensor gold-plated 060L117166
KP 78 30 – 90 5 – 15 150 2 silver 060L118466
KP 79 50 – 100 5 – 15 150 2 silver 060L112666
KP 81 80 – 150 7 – 20 200 2 silver 060L112566
KP 81 80 – 150 7 – 20 200 3 silver 060L118366
KP 81 80 – 150 7 – 20 200 5 silver 060L117066
KP 81
(max. reset)
80 – 150
8
(max. reset)
200 2 silver 060L115566
Ordering
Single thermostat