Data sheet | Pressure switch and Thermostat, KP and KPI
Safety cut-out setting
The righthand bellows will automatically cut-out
the pump at the safety cut-out setpoint.
Automatic start-up, if any, will take place when
the pressure has reached the level of 1 bar above
the setpoint. Manual cut-in is made by lifting the
impulse lever and releasing it again when the
pressure has increased by min. 1 bar.
The safety cut-out setpoint is normally
determined by the static pressure (the water
column). However, in order to avoid disturbing
signal interaction, care should be taken to ensure
that the safety cut-out setting is at least 1.5 bar
lower than the control pressure cut-in setting.
See table with pressure setting examples below.
Control pressure settings
Control pressure cut-out setpoint
is set on the lefthand pressure setting scale.
The differential is set between 0.7 and 4 bar.
The control pressure cut-in setting will be the
cut-out control pressure less the differential.
Setting
Accessories for KP 44
pressure switches
Net weight approx. 0.5 kg
Dimensions[mm]
and weights [kg]
Required tap water pressure ≥ 2.3 bar ≥ 4.0 bar ≥ 5.0 bar ≥ 8.0 bar
Control pressure cut-out setting 3.0 bar 5.0 bar 8.0 bar 12 bar
Differential 0.7 bar 1.0 bar 3.0 bar 4.0 bar
Control pressure cut-in setting 2.3 bar 4.0 bar 5.0 bar 8.0 bar
Max. safety cut-out setting 0.8 bar 2.5 bar 3.5 bar 6.0
1
bar
1
)
6.0 bar is the normal max. setpoint